1
Controls, Start-- Up, Operation
and Troubleshooting
48/50FC 04---07, 48/50GC 04---06
Single P ackage Rooft op Units
with SystemV u™ Controls Version 1.X
and Puronr (R---410A) Refr ig er ant
C150173
IMPORTANT: This literature covers 48/50FC 04--07 and 48/50GC 04--06 models with SystemVu controls version 1.X (factory--installed
option).
TABLE OF CONTENTS
Page
SAFETY CONSIDERATIONS 2.........................
GENERAL 3.........................................
Conventions Used in This Manual 3......................
BASIC CONTROL USAGE 3...........................
SystemVu Control (factory --installed option) 3..............
SystemVu Interface 3.................................
Accessory Navigatort Display 4........................
System Pilott andTouchPilott Devices 5................
CCN Tables and Display 5.............................
START -- UP 6.........................................
Unit Preparation 6....................................
Refrigerant Service Ports 6.............................
Crankcase Heater 6...................................
Compressor Rotation 6................................
Power Supply 6.....................................
Internal Wiring 6.....................................
Evaporator Fan 6....................................
Condenser Fans and Motors 6...........................
Return--Air Filters 8..................................
Outdoor--Air Inlet Screens 8............................
Accessory Installation 8...............................
Gas Heat (48FC and 48GC) 8...........................
CONTROLS QUICK SET-- UP 8.........................
Control Set Point and Confirmation Log 8.................
Initial Startup 8......................................
Thermostat Control 9.................................
Space T emperature Sensor Control -- Direct Wired
(T--55 or T--56 or T--59) 9.............................
Space Humidistat Control 9............................
Space Relative Humidity Sensor Control 9.................
CCN Communication 9...............................
CCN Linkage Control 9...............................

Table of Contents

Questions and Answers

  • C
    Christopher MilesSep 23, 2025
    What does Alert A110 mean on my Carrier Air Conditioner?
    • W
      William EdwardsSep 23, 2025
      Alert A110 on your Carrier Air Conditioner indicates that the SPT sensor is out of range. This is usually due to a faulty thermistor or an incorrect thermistor caused by improper ohm reading. When this alert is active, cooling and heating will not operate.
  • J
    Joshua MackAug 23, 2025
    What does Fault F010 mean on my Carrier 50GC 05 Air Conditioner?
    • J
      Jessica DavilaAug 23, 2025
      Fault F010 on your Carrier Air Conditioner indicates a low voltage issue, possibly due to a brownout, low supply voltage, or a missing phase in the supply power. The control system will shut down the unit, but it should automatically clear once the supply voltage rises above 19 volts AC.
  • J
    Jamie FrazierAug 25, 2025
    What does Fault F011 mean on my Carrier 50GC 05?
    • D
      Danny HowardAug 25, 2025
      Fault F011 indicates that the MBB reference voltage is out of range, usually due to an MBB failure or the supply voltage being out of range. The control system will shut down the unit. This fault should automatically clear when the DC reference voltage returns to its normal range.
  • J
    Jesse BeckAug 26, 2025
    What does Alert A012 mean on my Carrier 50GC 05?
    • M
      Mr. James BakerAug 27, 2025
      Alert A012 on your Carrier Air Conditioner signals an MBB zero crossing issue, often caused by an MBB failure or the supply voltage frequency being too high or too low. The alert should automatically clear once the supply voltage returns to the normal range.
  • H
    Heather KingAug 27, 2025
    What does Fault F013 mean on my Carrier 50GC 05?
    • D
      Doris MullinsAug 28, 2025
      Fault F013 on your Carrier Air Conditioner indicates that MBB Fuse 2 is open, typically due to a wiring error in a switch input or the switch pulling too much current. The control will shut down the unit, but the fault should automatically clear when the fuse temperature returns to normal.
  • S
    Stephen Foster MDSep 18, 2025
    What does Alert A107 mean on my Carrier 50GC 05?
    • A
      Angela MaysSep 18, 2025
      Alert A107 on your Carrier Air Conditioner indicates that the RAT sensor is out of range. This is usually due to a faulty thermistor, a shorted or open thermistor caused by a wiring error, or a loose connection. When this alert is active, no differential dry bulb crossover control can occur.
  • D
    Derek FloresSep 15, 2025
    What does Alert A105 mean on my Carrier 50GC 05?
    • A
      alangSep 15, 2025
      Alert A105 on your Carrier Air Conditioner indicates an open OAT sensor, generally caused by a faulty thermistor or an open thermistor due to a wiring error, or a loose connection. When this alert appears, the economizer will not operate for cooling.
  • K
    Krystal AdamsSep 16, 2025
    What does Alert A106 mean on my Carrier Air Conditioner?
    • J
      Jennifer ChambersSep 16, 2025
      Alert A106 on your Carrier Air Conditioner indicates a shorted OAT sensor, which is typically caused by a faulty thermistor or a shorted thermistor due to a wiring error, or a loose connection. If this alert is active, the economizer will not operate to provide cooling.
  • D
    davidbennettSep 6, 2025
    What does Fault F020 mean on my Carrier 50GC 05 Air Conditioner?
    • R
      Richard PriceSep 6, 2025
      Fault F020 on your Carrier Air Conditioner indicates a software error, meaning the software on the MBB is not responding. Recovery is automatic if the software can reset the board. If not, try cycling the power to the control before considering board replacement.
  • L
    Lisa HenrySep 3, 2025
    What does Fault F018 mean on my Carrier 50GC 05 Air Conditioner?
    • E
      Eric JonesSep 4, 2025
      Fault F018 on your Carrier Air Conditioner indicates an MBB EEPROM failure, meaning the serial EEPROM chip on the MBB, which stores the unit’s configuration, is not responding. Recovery is automatic, but you might need to replace the MBB board. Before replacing the board, try cycling the power to the control.

Summary

Controls, Start-Up, Operation and Troubleshooting

SAFETY CONSIDERATIONS

General safety precautions for installation, servicing, and maintenance of HVAC equipment.

BASIC CONTROL USAGE

Explains the SystemVu control system and its interface for unit management.

START-UP

CONTROLS QUICK SET-UP

Quick Setup

CCN Communication

Details configuration steps for CCN communication.

SERVICE TEST

Cooling Test

Heating Test

Automatic Test

CONTROLS OPERATION

Unit Configuration

Contains configurations for factory options and field accessories.

General Operation

Space Sensor Demand

Occupancy Determination

Indoor Fan Operation

Cooling Staging Control

Humidi-MiZer System Modes

Indoor Fan Based Dehumidification

Heating Operation

Economizer Operation

Free Cooling

Carrier Comfort Network (CCN) Operation

BACnet Network Operation

Alarm Handling

TROUBLESHOOTING

Shows operating conditions and provides troubleshooting steps.

Faults and Alerts

Indicates active alarms and provides methods for viewing and clearing them.

Cooling Troubleshooting

Compressor and Fan Will Not Start.

Lists causes and remedies for the compressor and fan failing to start.

Humidi-MiZer System Troubleshooting

Economizer Troubleshooting

Heating Troubleshooting

Phase Protection

Thermistor Troubleshooting

Transducer Troubleshooting

Main Base Board (MBB)

Integrated Gas Control (IGC) Board

Protective Devices

Carrier Comfort Network (CCN) Interface

APPENDIX A: SystemVu Controller Display

Settings Main Menu Layout

Lists display text, expanded text, values, units, default, and points for Settings.

Service Main Menu Layout

Lists display text, expanded text, values, units, write status, and points for Service Menu.

Alerts;Faults Main Menu Layout

Lists display text, expanded text, values, write status, and points for Alerts/Faults.

Inputs Main Menu Layout

Lists display text, expanded text, values, units, write status, and points for Inputs.

Outputs Main Menu Layout

Lists display text, expanded text, values, units, write status, and points for Outputs.

APPENDIX B: SystemVu Controller Display

APPENDIX C: Navigatort Display

MODE - RUN STATUS

Lists Navigator display items for Run Status.

MODE - SERVICE TEST

Lists Navigator display items for Service Test.

MODE - INPUTS

Lists Navigator display items for Inputs.

MODE - OUTPUTS

Lists Navigator display items for Outputs.

MODE - CONFIGURATIONS

Lists Navigator display items for Configurations.

MODE - TIME CLOCK

Lists Navigator display items for Time Clock settings.

MODE - ALARMS

Lists Navigator display items for Alarms.

APPENDIX D: SystemVu Controller CCN Tables

Status Display Tables

Lists CCN table data for SystemVu controller status display.

APPENDIX D: SystemVut Controller CCN Tables

Service Config Tables

Lists configuration parameters for unit settings.

Maintenance Tables

Lists CCN table data for system maintenance.

Setpoint Table

Lists setpoint values and their configurations.

APPENDIX E: BACnet Points List

CONTROL SET POINT AND CONFIGURATION LOG

Settings - Main Menu Layout (cont)

UNIT START-UP CHECKLIST

III. HUMIDI-MIZER SYSTEM START-UP

Carrier 50GC 05 Specifications

General IconGeneral
BrandCarrier
Model50GC 05
CategoryAir Conditioner
LanguageEnglish