Table 4--ElectricM Data--5OGS
UNiT 50GS
SIZE
030
038
042
048
060
V-PH-HZ
208/230-3-60
208/230-3-60
460-3-60
208/230-3-60
460-3-60
208/230-3-60
460-3-60
208/230-3-60
460-3-60
VOLTAGE
RANGE
Min Max
187 254
187 254
414 508
187 254
414 508
187 254
414 508
187 254
414 508
COMPRESSOR OFM IFM
RLA LRA FLA FLA
8.3 68 0.8 2
10.9 78 1.4 2.8
5.8 40 0.8 1.4
10.7 85 1.4 4
5.3 42 0.8 2
14.6 108 2.1 5
7.3 48 1.1 2.3
18.6 125 2.1 6.8
8.5 66.5 1.1 3.2
ELECTRIC HEAT
Nominal kW* FLA
-/- -/-
3.8/5.0 10.4/12.0
7.5/10.0 20.8/24.1
11.3/15.0 31.3/36.1
-/- -/-
3.8/5.0 10.4/12.0
7.5/10.0 20.8/24.1
11.3/15.0 31.3/36.1
5 6
10 12
15 18
-/-
10.4/12.0
3.8/5.0
20.8/24.1
7.5/10.0
31.3/36.1
11.3/15.0
41.6/48.0
15.0/19.9
5 6
10 12
15 18
20 24.1
-/- -/-
3.8/5.0 10.4/12.0
7.5/10.0 20.8/24.1
11.3/15.0 31.3/36.1
15.0/19.9 41.6/48.0
5 6
10 12
15 18
20 24.1
-/- -/-
3.8/5.0 10.4/12.0
7.5/10.0 20.8/24.1
11.3/15.0 31.3/36.1
15.0/19.9 41.6/48.0
5 6
10 12
15 18
20 24
POWER SUPPLY
MCA Max Fuse orCkt Bkr
13.2/13.2 20/20
15.5/17.5 20/20
28.6/32.6 30/35
41.6/47.6 45/50
17.8/17.8 25/25
16.5/18.5 25/25
29.6/33.6 30/35
42.6/48.6 45/50
9.5 15
9.5 15
16.8 20
24.3 25
25/25
18.8/18.8
25/25
31.1/35.1
35/40
44.1/50.1
45/60
57.0/65.0
9.4 15
10.0 15
17.5 20
25.1 30
32.6 35
25.4/25.4 30/30
25.4/25.4 30/30
32.3/36.3 35/40
45.3/51.4 50/60
58.2/66.2
12.5 15
12.5 15
17.9 20
25.4 30
32.9 35
32.2/32.2 40/40
32.2/32.2 40/40
34.6/38.6 40/40
47.6/53.6 50/60
60.5/68.5
14.9 20
14.9 20
19.0 20
26.6 30
34.1 35
MOCP
60/70
60/70
70/70
(See legend following Electrical Data charts)
STANDARD CONNECTION
Remove knockout hole located in the electric heat panel adjacem
to the control access panel. See Fig. g & 3. Remove the rubber
grommet l_'om the installer's packet (included with unit) and install
grommet in the knockout opening. Provide a drip loop belbre
running wire through panel.
Run the low-voltage leads l}'om the thermostat, through the inlet
hole, and into unit low-voltage splice box.
Locate five 18-gauge wires leaving control box. These low-voltage
connection leads can be identified by the colors red, green, yellow,
brown, and white (See Fig. 10). Ensure the leads are long enough
to be routed into the low-voltage splice box (located below right
side of control box). Stripped yellow wire is located in connection
box. Route leads through hole in bottom of control box and make
low-voltage connections (See Fig. 10). Secure all cut wires, so that
they do not interli:re with operation of unit.
TRANSFORMER PROTECTION
The tran._fbrtnur is ol' the energy-limiting type. It is set to
withstand a 30-second overload or shorted secondary condition.
P
HIGH VOLTAGE |
POWER LEADS <o=
(SEE UNITWIRINGI
LABEL) [?=
CONTROLBOX
LOW-VO LTAG E
POWER LEADS-
(SEE UNIT
WIRING LABEL)
m
m = =_o
.E f.
,[--
GND
SPLICE BOX
LEGEND
Field Control-Voltage Wiring
Field High-Voltage Wiring
: _LPOWER
.... '_ _ = 4jSUPPLY
FIELD-SUPPLIED
FUSED DISCONNECT
YE==Lff).= ,D,=@ THERMOSTAT
-GRN(G2 _ @ |(TYPICAL)
REUaj.O" @
J
BRN(._C! ,,_ @
C99010rev2
Fig. 10--High- and Control-Voltage Connections
II