13
Performance data (cont)-Standard PSC indoor motor
COOLING EXTENDED PERFORMANCE TABLE
HEATING EXTENDED PERFORMANCE TABLE -10–20
HEATING EXTENDED PERFORMANCE TABLE 30–60
*At 75°F entering dry bulb—Tennessee Valley Authority [TVA] rating conditions; all others at 80°F entering dry bulb.
See Legend and Notes on page 17.
50JZ036 COOLING PERFORMANCE TABLE
Temp (F)
Outdoor Air
Entering
Condenser
Evaporator Air—CFM/BF
1050/0.07 1200/0.08 1350/0.10
Evaporator Air — Ewb (F)
62 63* 67 72 62 63* 67 72 62 63* 67 72
75
TC 35.9 36.2 39.8 42.4 37.0 37.1 40.5 42.8 37.6 37.2 40.5 42.8
SHC 32.7 26.5 27.7 22.2 35.2 28.1 29.0 22.9 36.7 29.1 29.8 23.2
kW 2.66 2.76 2.70 2.70 2.76 2.87 2.80 2.81 2.87 3.03 2.96 2.96
85
TC 33.9 34.0 38.0 41.4 35.0 34.8 38.9 41.9 35.9 35.0 39.0 41.9
SHC 31.9 25.5 27.3 22.0 34.4 27.2 28.9 22.7 35.6 28.4 29.9 23.1
kW 2.91 3.04 2.98 2.98 3.01 3.17 3.09 3.09 3.11 3.32 3.25 3.25
95
TC 31.7 31.6 36.1 39.8 32.7 32.3 36.6 40.3 33.9 32.5 36.8 40.3
SHC 30.5 24.3 26.6 21.4 32.7 25.9 28.2 22.3 33.9 27.1 29.4 22.8
kW 3.16 3.32 3.31 3.29 3.25 3.45 3.40 3.40 3.39 3.60 3.55 3.56
105
TC 28.5 28.0 32.0 36.1 29.7 28.7 32.7 36.6 30.6 28.8 32.9 36.6
SHC 27.9 22.3 24.3 19.8 29.7 23.8 26.1 20.8 30.6 25.0 27.4 21.3
kW 3.52 3.69 3.67 3.70 3.62 3.82 3.81 3.81 3.78 3.97 3.95 3.97
115
TC 26.1 25.4 29.0 33.5 27.5 25.9 29.6 33.8 28.3 26.0 29.8 33.7
SHC 26.0 21.1 22.9 18.8 27.5 22.5 24.5 19.7 28.3 23.6 25.9 20.3
kW 3.85 4.00 4.01 4.05 3.96 4.15 4.13 4.18 4.11 4.28 4.29 4.33
125
TC 23.9 22.2 26.0 29.9 25.2 22.6 26.5 30.4 25.8 23.0 26.6 30.3
SHC 23.9 19.5 21.5 17.4 25.2 20.9 23.1 18.4 25.8 21.9 24.2 19.1
kW 4.26 4.41 4.40 4.48 4.38 4.51 4.52 4.60 4.54 4.64 4.66 4.76
50JZ036
Return
Air (F db)
CFM (Standard Air)
Air Temperature Entering Outdoor Coil (F db at 70% rh)
-100 101720
60
1050
TC
7.2
6.1 11.2 9.5 15.3 14.0 18.4 16.7 19.9 18.0
kW
2.43 2.47 2.51
2.54 2.56
1200
TC
7.4
6.3 11.5 9.8 15.6 14.3 18.7 17.0 20.2 18.2
kW
2.47 2.50 2.53 2.55 2.57
1350
TC
7.6
6.5 11.7 10.0 15.8 14.5 19.0 17.3 20.6 18.5
kW
2.51 2.53 2.56 2.57 2.60
70
1050
TC
6.3
5.4 10.3 8.7 14.2 13.1 17.4 15.9 19.0 17.1
kW
2.64 2.68 2.73
2.77 2.79
1200
TC
6.5
5.6 10.5 9.0 14.5 13.3 17.8 16.2 19.3 17.4
kW
2.68 2.71 2.75 2.78 2.79
1350
TC
6.7
5.7 10.8 9.2 14.8 13.6 18.1 16.5 19.7 17.7
kW
2.72 2.75 2.77 2.79 2.81
80
1050
TC
5.2
4.4 9.2 7.8 13.2 12.1 16.3 14.8 17.8 16.1
kW
2.86 2.91 2.97
3.01 3.03
1200
TC
5.4
4.6 9.5 8.0 13.5 12.4 16.7 15.2 18.2 16.4
kW
2.90 2.94 2.98 3.02 3.03
1350
TC
5.6
4.8 9.7 8.2 13.8 12.6 17.0 15.5 18.6 16.7
kW
2.94 2.98 3.01 3.03 3.05
50JZ036
Return
Air (F db)
CFM (Standard Air)
Air Temperature Entering Outdoor Coil (F db at 70% rh)
30 40 47 50 60
60
1050
TC
25.1
22.0 30.9 30.9 35.2 35.2 36.9 36.9 42.8 42.8
kW
2.65 2.80 2.89
2.92 3.02
1200
TC
25.5
22.3 31.4 31.4 35.8 35.8 37.3 37.3 43.2 43.2
kW
2.65 2.79 2.86 2.88 2.96
1350
TC
25.8
22.6 31.8 31.8 36.1 36.1 37.7 37.7 43.9 43.9
kW
2.67 2.79 2.85 2.86 2.94
70
1050
TC
24.1
21.1 30.1 30.1 34.6 34.6 36.3 36.3 42.7 42.7
kW
2.85 3.00 3.16
3.21 3.34
1200
TC
24.5
21.5 30.6 30.6 35.2 35.2 36.9 36.9 43.2 43.2
kW
2.85 2.99 3.13 3.17 3.27
1350
TC
24.9
21.8 31.0 31.0 35.7 35.7 37.4 37.4 43.6 43.6
kW
2.86 3.00 3.12 3.14 3.23
80
1050
TC
22.9
20.1 28.8 28.8 33.5 33.5 35.2 35.2 42.2 42.2
kW
3.10 3.21 3.40
3.45 3.68
1200
TC
23.4
20.5 29.3 29.3 34.1 34.1 35.8 35.8 42.8 42.8
kW
3.09 3.20 3.37 3.42 3.60
1350
TC
23.8
20.9 29.7 29.7 34.6 34.6 36.3 36.3 43.2 43.2
kW
3.09 3.20 3.35 3.40 3.55