EasyManua.ls Logo

Carrier 50KC04-06 - Convenience Outlets; Non-Powered Type; Unit-Powered Type

Carrier 50KC04-06
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18
CONVENIENCE OUTLETS
Two types of convenience outlets are offered on 50KC models:
non-powered and unit-powered. Both types provide a 125-v
GFCI (ground-fault circuit-interrupter) duplex receptacle rated
at 15-A behind a hinged waterproof access cover, located on
the end panel of the unit. See Fig. 21.
Fig. 21 — Convenience Outlet Location
Non-Powered Type
This type requires the field installation of a general-purpose
125-v 15-A circuit powered from a source elsewhere in the
building. Observe national and local codes when selecting wire
size, fuse or breaker requirements and disconnect switch size
and location. Route 125-v power supply conductors into the
bottom of the utility box containing the duplex receptacle.
Unit-Powered Type
A unit-mounted transformer is factory-installed to stepdown
the main power supply voltage to the unit to 115-v at the du-
plex receptacle. This option also includes a manual switch with
fuse, located in a utility box and mounted on a bracket behind
the convenience outlet; access is through the unit’s control box
access panel. See Fig. 21.
The primary leads to the convenience outlet transformer are
not factory-connected. Selection of primary power source is a
customer option. If local codes permit, the transformer primary
leads can be connected at the line-side terminals on a unit-
mounted non-fused disconnect or HACR breaker switch; this
will provide service power to the unit when the unit disconnect
switch or HACR switch is open. Other connection methods
will result in the convenience outlet circuit being de-energized
when the unit disconnect or HACR switch is open. See Fig. 22.
Fig. 22 — Powered Convenience Outlet Wiring
Head pressure too low
Low refrigerant charge. Check for leaks; repair and recharge.
Compressor valves leaking. Replace compressor.
Restriction in liquid tube. Remove restriction.
Excessive suction pressure
High head load. Check for source and eliminate.
Compressor valves leaking. Replace compressor.
Refrigerant overcharged. Recover excess refrigerant.
Suction pressure too low
Dirty air filter. Replace filter.
Low refrigerant charge. Check for leaks; repair and recharge.
Metering device or low side restricted. Remove source of restriction.
Insufficient evaporator airflow.
Increase air quantity. Check filter and replace if
necessary.
Temperature too low in conditioned area. Reset thermostat.
Outdoor ambient below 25°F Install low-ambient kit.
Evaporator fan will not shut off Time off delay not finished. Wait for 30-second off delay.
Compressor makes excessive noise Compressor rotating in wrong direction. Reverse the 3-phase power leads.
Table 1 — Cooling Service Analysis (cont)
PROBLEM CAUSE REMEDY
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury
or death.
Units with convenience outlet circuits may use multiple
disconnects. Check convenience outlet for power status before
opening unit for service. Locate its disconnect switch, if
appropriate, and open it. Tag-out and lock this switch.
CONVENIENCE
OUTLET GFCI
PWD-CO FUSE
SWITCH
PWD-CO TRANSFORMER
CONTROL BOX
ACCESS PANEL
UNIT
VOLTAGE
CONNECT
AS
PRIMARY
CONNECTIONS
TRANSFORMER
TERMINALS
208, 230 240
L1: RED +YEL
L2: BLU + GRA
H1 + H3
H2 + H4
460 480
L1: RED
Splice BLU + YEL
L2: GRA
H1
H2 + H3
H4
575 600
L1: RED
L2: GRA
H1
H2

Table of Contents

Related product manuals