EasyManua.ls Logo

Carrier 50KC04-06 - Page 68

Carrier 50KC04-06
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
68
Legend and Notes for Tables P-X.
LEGEND
NOTES:
1. In compliance with NEC requirements for multimotor and combina-
tion load equipment (refer to NEC Articles 430 and 440), the over-
current protective device for the unit shall be fuse or HACR
breaker. Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage
is greater than 2%. Use the following formula to determine the per-
centage of voltage imbalance.
% Voltage Imbalance:
Example: Supply voltage is 230-3-60
Determine maximum deviation from average voltage.
(AB) 227-224 = 3 v
(BC) 231-227 = 4 v
(AC) 227-226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
This amount of phase imbalance is satisfactory as it is below the maxi-
mum allowable 2%.
NOTE: Check all factory and field electrical connections for tightness.
Table R — 50KC**06 (5 Tons) Cooling
v-Ph-Hz
UNIT VOLTAGE COMP 1 OFM (ea) IFM
RANGE
RLA LRA WATTS FLA TYPE
EFF at Full
Load
FLA
MIN MAX
208-1-60 187 253 25.0 134
325 1.4 DD-STD 78% 7.4
325 1.4 MED 76% 7.0
230-1-60 187 253 25.0 134
325 1.4 DD-STD 78% 7.4
325 1.4 MED 76% 7.0
208-3-60 187 253 15.9 110
325 1.4 DD-STD 78% 7.4
325 1.4 MED 89% 8.4
325 1.4 HIGH 89% 8.4
230-3-60 187 253 15.9 110
325 1.4 DD-STD 78% 7.4
325 1.4 MED 89% 8.3
325 1.4 HIGH 89% 8.3
460-3-60 414 506 7.0 52
325 0.9 DD-STD 78% 4.0
325 0.9 MED 89% 4.2
325 0.9 HIGH 89% 4.2
575-3-60 518 633 5.1 40
325 0.9 DD-STD 78% 4.0
325 0.9 MED 77% 2.8
325 0.9 HIGH 77% 2.8
BRKR Circuit breaker
C.O. Convenience outlet
DISC Disconnect
FLA Full load amps
IFM Indoor fan motor
LRA Locked rotor amps
MCA Minimum circuit amps
P.E. Power exhaust
pwrd fr/ unit Powered from unit
PWRD C.O. Powered convenience outlet
UNPWR C.O. Unpowered convenience outlet
= 100 x
max voltage deviation from average voltage
average voltage
AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage =
(224 + 231 + 226)
=
681
= 227
33
% Voltage Imbalance = 100x
4
=1.78%
227
IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.
A
B
C
MOTOR

Table of Contents

Related product manuals