APPENDIX C: Navigatort Display
MODE -- TEMPERATURES
ITEM EXPANSION RANGE UNIT
WRITE
STATUS
POINT
TEMPERATURES
SAT Supply Air Temperature xxx.x °F SAT
OAT Outdoor Air Temperature xxx.x °F YES OAT
RAT Return Air Temperature xxx.x °F YES RAT
SPT Space Temperature xxx.x °F YES SPACE_T
SPTO Space Temperature Offset xx.x °F YES SPTO
SST.A Cir.A Sat. Suction Temp xxx.x °F SST_A
SDT.A Cir.A Sat. Discharge Temp xxx.x °F SDT_A
FST Fan Supply Air Temp xxx.x °F FST
MODE -- PRESSURES
ITEM EXPANSION RANGE UNIT
WRITE
STATUS
POINT
PRESSURES
SSP.A Cir. A Suction Pressure xxx.x psig SSP_A
SDP.A Cir . A Discharge Pressure xxx.x psig SDP_A
PR.A Circuit A Pressure Ratio xx.xx n/a CIRA_PR
BARP Barometric Pre ssure xx.xx in.Hg YES BARP
MODE -- SETPOINTS
ITEM EXPANSION RANGE UNIT DEFAULT POINT
SETPOINTS
OCSP Occupied Cool Setpoint 55 to 80 °F 78 OCSP
OHSP Occupied Heat Setpoint 55 t o 80 °F 68 OHSP
UCSP Unoccupied Cool Setpoint 65 to 95 °F 85 UCSP
UHSP Unoccupied Heat Setpoint 40 to 80 °F 60 UHSP
GAP Heat--- Cool Setpoint Gap 2to10 ^F 5 HCSP_GAP
STO.R SPT Offset Range (+/--- ) 0to5 °F 5 SPTO_RNG
RH.SP Space RH Setpoint 0 t o 100 % 55 SPRH_SP
SA.SP SA t empering Set point xx °F 50 SATEMPSP
T. D M D Temp Demand Config Menu
LCON Low Cool Demand On --- 1 t o 2 °F 0.5 DMDLCON
MCON Medium Cool Demand On 0.5 to 20 °F 1 DMDMCON
HCON H igh Cool Demand On 0.5 to 20 °F 2 DMDHCON
LCOF Low Cool Demand Off --- 1 t o 2 °F --- 0 . 5 DMDLCOFF
CLUP Cool Demand Level Up --- 2 t o 2 ^F/min --- 0 . 2 CDMD_LUP
LHON Low Heat Demand On --- 1 t o 2 °F 0.5 DMDLHON
HHON High Heat Demand On 0.5 to 20 °F 2 DMDHHON
LHOF Low Heat Demand Off --- 1 t o 2 °F --- 0 . 5 DMDLHOFF
HLUP Heat Demand Level Up --- 2 t o 2 ^F/min --- 0 . 2 HDMD_LUP
TG1 Space Demand Time Guard1 60 t o 600 sec 180 TDMD_TG1
TG2 Space Demand Time Guard2 0 t o 600 sec 300 TDMD_TG2
TG3 Space Demand Time Guard3 5 t o 120 min 10 TDMD_TG3
DMD.C Demand Limit Config Menu
CDL.1 COOL DMD Offset level 1 0to99 °F 1 CLDOLEV1
CDL.2 COOL DMD Offset level 2 0to99 °F 3 CLDOLEV2
CDL.3 COOL DMD Offset level 3 0to99 °F 5 CLDOLEV3
HDL.1 Heat DMD Offset level 1 0to99 °F 1 HTDOLEV1
HDL.2 Heat DMD Offset level 2 0to99 °F 3 HTDOLEV2
HDL.3 Heat DMD Offset level 3 0to99 °F 5 HTDOLEV3