110
APPENDIX C: Navigatort Display
MODE -- CONFIGURATIONS (cont)
ITEM EXPANSION RANGE UNIT DEFAULT POINT
ODF (cont) Outdoor Fans Config Menu
BS3 ODF Map Bias Term 3 --- 200 to 200 0 (sizes 07, 14--- 20)
65.29 (sizes 08--- 12)
114.74 (sizes 24--- 26)
ODFBIAS3
PI1 ODF Fan Switch Point 1 --- 100 to 100 3.68 (size 07)
3.4 (sizes 08--- 12)
4.84 (sizes 14--- 20)
1.58 (sizes 24--- 26)
ODFPIUP1
PI2 ODF Fan Switch Point 2 --- 100 to 100 17.1 (size 07)
9.06 (sizes 08--- 12)
22.3 (sizes 14--- 20)
10.44 (sizes 24--- 26)
ODFPIUP2
PI3 ODF Fans Switch Point 3 --- 100 to 100 100 (sizes 07, 14--- 20)
19.76 (sizes 08--- 12)
20.93 (sizes 24--- 26)
ODFPIUP3
PR.KC ODF Proportional ctrl Pr --- 100 to 100 25 (sizes 07--- 12)
50 (sizes 14--- 26)
ODFPR_KC
SLP1 ODF Map Slope Term 1 --- 100 to 100 25.3 (size 07)
60.09 (sizes 08--- 12)
31 (sizes 14--- 20)
55.33 (sizes 24--- 26)
ODFSLPE1
SLP2 ODF Map Slope Term 2 --- 100 to 100 9 (size 07)
18.69 (sizes 08--- 12)
9.6 (sizes 14--- 20)
19.07 (sizes 24--- 26)
ODFSLPE2
SLP3 ODF Map Slope Term 3 --- 100 to 100 1 (sizes 07, 14--- 20)
9.34 (sizes 08--- 12)
8.85 (sizes 24--- 26)
ODFSLPE3
HEAT HeatingConfigMenu
HT.TY Type of Heat Installed 0=ELECTRIC,
1=GAS
0(50series)
1(48series)
HEATTYPE
N.HTR Number of Heating Stages 0to2 2 (all except below);
0(50serieswithoutFIOP
heat)
1 (50 series, sizes 07--- 14
and low heat)
1 (50 series, sizes 07--- 12
and medium heat)
NUMHSTGS
HMRT Heat Minimum On Time 60 to 600 sec 120 H_MINON
HMOT Heat Minimum Off Time 60 to 600 sec 120 H_MINOFF
H.INC Heat Stage Increase Time 120 t o 999 sec 450 HSTAGINC
TLH Heating SAT Trend Level --- 1 t o 1 ^F/min 0.2 SAT_TLH
SAM.L Heat Max SAT Lower Level 85 t o 200 °F 140 SATMAX_L
SAM.U Heat Max SAT Upper Level 85 to 200 °F 160 SATMAX_H
H.FOD Heating Fan--- off Delay 10 t o 600 sec 30 (50 series)
45 (48 series)
HEAT_FOD
HT.LO Heating Lockout Temp 40 t o 125 °F 75 OATLHEAT
SAT.H SAT Heat Mode Sensing Enable/Disable Disable SAT_HEAT
N.IFO No IGC IFO input Timeout 0to60 min 5 NO_IGCTM
PREH Pre--- Heat HX without IDF? Enable/Disable Disable PREHT_HX
PH.DY Pre---HeatFanOnDelay 0 to 120 sec 30 PREHT_TM
SA.EN Supply Air Tempering Enable Yes/No Yes SATEMPEN
SA.SP SA Tempering Set Point xx °F 50 SATEMPSP
OAT.S Max OAT for SA Tempering --- 40 to 125 °F 48 OATSTEMP
I.FAN Indoor Fan Config Menu
OC.FN FanOnWhenOccupied Yes/No Yes FANON_OC
IDF.F Shut Down on IDF Failure Yes/No Yes FAT ALFAN
S.MIN IDF Min RPM SP xxxx RPM 0 RPMMINSP
S.MAX IDF Max RPM SP xxxx RPM 0 RPMMAXSP
FS.LC Low Cooling IDF Speed 20--- 100 % 67 (sizes 07--- 12)
53 (sizes 14 or 20)
56 (size 17)
52 (size 24)
60 (size 26)
FSPD_LCL
FS.FC Free Cooling IDF Speed 0 --- 1 0 0 % 67 (sizes 07--- 12)
53 (sizes 14 or 20)
56 (size 17)
52 (size 24)
60 (size 26)
FSPD_FCL
FS.HC High Cooling IDF Speed 20--- 100 % 100 FSPD_HCL
S.HT IDF He at RPM SP xxxx RPM 0 RPM_HEAT
S.VNT IDF Vent RPM SP xxxx RPM 0 RPM_VENT
C.LOP IDF curve PWM min 0 --- 1 0 0 % 0 IFMLOPWM
C.HIP IDF curve PWM ma x 0 --- 1 0 0 % 0 IFMHIPWM
C.LOR IDF curve RPM min xxxx RPM 0 IFMLORPM
C.HIR IDF curve RPM max xxxx RPM 0 IFMHIRPM