APPENDIX D: SystemVut Controller CCN Tables
Service Config Tables
Tab le N am e Display Name Range Units Point Name Default
TOUCH
Equip Sys Touch Active enum ETST_ACT
Equipment Touch SPT _F ETSPT
Equipment Touch RH % ETSPRH
System Touch Temp Value _F STST_NET
System Touch SPRH Value % STRH_NET
ET ST Aggregated SPT _F ETSTSPT
ET ST Aggregated SPRH % ETSTSPRH
UNIT_CFG
Unit Startup Delay 10 to 600 sec ST ARTDLY 30
Auxiliary vent type 1 VENTTYPE
Unit Control Type 0=Thermostat,
1=SpaceSensor,
2 = RAT Control
CTRLTYPE 0=TSTAT
Thermostat Hardware Type 0=2StageConventional,
1=2StageDigital,
2=3StageConventional,
3=3StageDigital
STATTYPE 2=CONV 3C2H
Tstat Adaptive Staging Yes/No ADPTSTAT Yes
Change Filter Timer 0 to 9999 hours FILTLIFE 600
Test Inactivity Time Out 0=Disabled,
1 = 30 Minutes,
2=1Hour,
3=2Hours,
4=4Hours,
5=8Hours,
6=12Hours
TEST_ITO 4=4 hours
CCH Max Temperature 40 to 90 °F CCHMAXT 65
Std Barometric Pressure 13 to 35 in.Hg STD_BARP 29.92
Linkage Stage inc. time 60 to 600 sec LSTAGINC 180
Unit’s Maximum SAT 130 to 210 °F UMAX_SAT 200
Auto Clr SAT Limit Fault Yes/No SATLACLR No
Adaptive Temp Comp Start Enable/Disable TCS_CFG Yes
User TCS Start bias time 0 t o 180 min TCSUBIAS 0
SIOB 1 Enabled Yes/No SIOB1_EN
Compressor A1 Enabled Enable/Disable CMPA1_EN
Compressor A2 Enabled Enable/Disable CMPA2_EN
Compressor AL Enabled Enable/Disable CMPAL _EN
Compressor A1 Shutdown Enable/Disable SDWN_A1
Compressor A2 Shutdown Enable/Disable SDWN_A2
cmp Loader Shutdown Enable/Disable SDWN_ALD
DMD_CFG
Low Cool Demand On --- 1 t o 2 °F DMDLCON 0.5
Medium Cool Demand On 0.5 to 20 °F DMDMCON 1
High Cool Demand On 0.5 to 20 °F DMDHCON 2
Low Cool Demand Off --- 1 t o 2 °F DMDLCOFF --- 0 . 5
Cool Demand Level Up --- 2 t o 2 ^F/min CDMD_LUP --- 0 . 2
Low Heat Demand On --- 1 t o 2 °F DMDLHON 0.5
High Heat Demand On 0.5 to 20 °F DMDHHON 2
Low Heat Demand Off --- 1 t o 2 °F DMDLHOFF --- 0 . 5
Heat Demand Level Up --- 2 t o 2 ^F/min HDMD_LUP --- 0 . 2
Space Demand Time Guard1 60 to 600 sec TDMD_TG1 180
Space Demand Time Guard2 0 to 600 sec TDMD_TG2 300
Space Demand Time Guard3 5 to 120 min TDMD_TG3 10
COOL DMD Offset level 1 0to99 °F CLDOLEV1
COOL DMD Offset level 2 0to99 °F CLDOLEV2
COOL DMD Offset level 3 0to99 °F CLDOLEV3
Heat DMD Offset level 1 0to99 °F HTDOLEV1
Heat DMD Offset level 2 0to99 °F HTDOLEV2
Heat DMD Offset level 3 0to99 °F HTDOLEV3