89
APPENDIX A: SystemVut Controller Display
Service Main Menu L ayout
Display Text Expanded Text Values Units Write Status Point
SERVICE Service Menu
UNIT TEST S Unit Tests Menu
TEST MODE ServiceTestModeEnable On/Off Command
SERVICE TEST Service Test Menu
INDEPENDENTS INDEPENDENT TEST MENU
ECON POS TEST Economizer Position Test 0 to 100 % Command S_DAMPER
BUMP COMP A1 TEST Compressor Bump A1 Test On/Off On/Off Command S_BMPA1
BUMP COMP A2 TEST Compressor Bump A2 Test On/Off On/Off Command S_BMPA2
LIQ DIVERT A TEST LiqDivertrValveRelayTest On/Off On/Off Command S_LDV_A
REHEAT A TEST ReheatDischgValveRelayTest On/Off On/Off Command S_RDV_A
R E H E A T LV --- A T E S T Reheat Liq Valv Rly Test On/Off On/Off Command S_RLV_A
COOLING LV--- A TEST Cooling Liq Valv Test On/Off On/Off Command S_CL V_A
CCH RELAY 1 TEST Crankcase Heater 1 test On/Off On/Off Command S_CCHR1
ALARM RELAY TEST Alarm Output Relay Test On/Off On/Off Command S_ALARM
PE1 RELAY TEST Power Exhaust 1 Test On/Off On/Off Command S_PE_1
PE2 RELAY TEST Power Exhaust 2 Test On/Off On/Off Command S_PE_2
FAN TESTS Indoor and Outdoor Fan tests Menu
IDF SPEED TEST Indoor Fan Speed Test 0 to 100 % Command S_IDFSPD
ALL ODF SPD TEST System ODF speed test 0 to 1200 rpm Command S_ODFSPD
ODF 1 SPEED TEST Outdoor Fan 1 speed test 0 to 1200 rpm Command S_ODFSP1
ODF 2 SPEED TEST Outdoor Fan 2 speed test 0 to 1200 rpm Command S_ODFSP2
ODF 3 SPEED TEST Outdoor Fan 3 speed test 0 to 1200 rpm Command S_ODFSP3
IDF MANUAL TRANS IDF Manual Transition Yes/No Command S_IDFTRN
ODF MANUAL TRANS ODF Manual Transition Yes/No Command S_ODFTRN
COOL TESTS Cooling Test Menu
COOL A1 TEST Cooling W/Comp.A1 Test On/Off Command S_COOLA1
COOL A2 TEST Cooling W/Comp.A2 Test On/Off Command S_COOLA2
IDF SPEED TEST Indoor Fan Speed Test 0 to 100 % Command S_IDFSPD
ALL ODF SPD TEST System ODF speed test 0 to 1200 rpm Command S_ODFSPD
HUMIDIMIZER TEST HumidiMizer Level 0=Off,
1=Subcool,
2=Reheat
Command S_HMZLEV
HEAT TESTS Heating Test Menu
HEAT 1 TEST Heating Stage 1 Test On/Off Command S_HEAT1
HEAT 2 TEST Heating Stage 2 Test On/Off Command S_HEAT2
IDF SPEED TEST Indoor Fan Speed Test 0 to 100 % Command S_IDFSPD
AUTOMATIC TEST Automatic Test Menu
AUTO INDP TEST AUTO INDEPENDENT TEST Ye s/No Command AUTOINDP
AUTO COOL TEST RUN AUTO COOLING TEST Ye s/No Command AUTOCOOL
AUTO HEAT TEST RUN AUTO HEATING TEST Yes/No Command AUTOHEAT
AUTO SYSTEM TEST RUN AUTO SYSTEM TEST Yes/No Command AUTOSYS
UNIT INFORMATION Unit Information Menu
MODEL # Equipment Model number xxxxxxxxxxxxxxxx Command EQ_MOD
SERIAL # Equipment Serial number xxxxxxxxxx Command EQ_SER
ENTER MODEL NUMBER Edit Equipment Model Number
VERSIONS Versions Menu
SOFTWARE Application SW Version CESR131651--- xx--- xx FW_CESR
VFD VFD1 SW V ersion FW VERSION--- x.xx VFD1_SW
IO BOARD SIOB1 SW V ersion SIOB1 SW VERSION--- x.xx SIOB1_SW
BOOTLOADER Bootloader SW Version CESR131659--- xx--- xx BL_CESR
USER MEASURED DATA User Measured Data Menu
SUPPLY VOLTAGE L1 Supply Voltage Leg 1 0 to 700.0 volt Command L1VOL TS
SUPPLY VOLTAGE L2 Supply Voltage Leg 2 0 to 700.0 volt Command L2VOL TS
SUPPLY VOLTAGE L3 Supply Voltage Leg 3 0 to 700.0 volt Command L3VOL TS
COMP A1 AMPS L1 Comp A1 Amps Leg 1 0 to 100.0 amps Command CA1L1_A
COMP A1 AMPS L2 Comp A1 Amps Leg 2 0 to 100.0 amps Command CA1L2_A
COMP A1 AMPS L3 Comp A1 Amps Leg 3 0 to 100.0 amps Command CA1L3_A
COMP A2 AMPS L1 Comp A2 Amps Leg 1 0 to 100.0 amps Command CA2L1_A
COMP A2 AMPS L2 Comp A2 Amps Leg 2 0 to 100.0 amps Command CA2L2_A
COMP A2 AMPS L3 Comp A2 Amps Leg 3 0 to 100.0 amps Command CA2L3_A
E.HEAT AMPS L1 Elec. Heat Amps Leg 1 0 to 100.0 amps Command EHTL1_A
E.HEAT AMPS L2 Elec. Heat Amps Leg 2 0 to 100.0 amps Command EHTL2_A
E.HEAT AMPS L3 Elec. Heat Amps Leg 3 0 to 100.0 amps Command EHTL3_A
GAS SUPPLY TYPE Gas Supply Type 0=NATURAL,
1=LP
Command GASTYPE
GAS INLET PRESS Gas Inlet Pressure 0 to 20.0 in.wc Command GASPRESS
STAGE 1 GAS PRESS Stage 1 Gas Pressure 0 to 20.0 in.wc Command HT1PRESS
STAGE 2 GAS PRESS Stage 2 Gas Pressure 0 to 20.0 in.wc Command HT2PRESS
CONTINUE? Start Diag Report Yes/No Command GO_DIAG