95
APPENDIX A: SystemVut Controller Display
Inputs Main Menu Layout (cont)
Display Text Expanded Text Values Units Write Status Point
GENERAL INPUTS (cont) General Inputs Menu
VFD FAULT DETAIL IDF VFD Fault Detail 0=NONE,
1=PWR CARD,
2=EARTH FLT,
3=CTRL WORD,
4=OVER CURR,
5=OVER TEMP,
6=OVERLOAD,
7=UNDERVOLT,
8=OVER VOLT,
9=SHORT CIR,
10=PHASELOSS,
11=U LOSS,
12=V LOSS,
13=W LOSS,
14=CTRL VOLT,
15=VDD L OW,
16=MULTIPLE,
17=UNEXPECT
SVFDFLT
VFD WARN DETAIL IDF VFD Wa rning Detail 0=NONE,
1=VOLTAGE,
2=CURRENT,
3=THERMAL,
4=MULTIPLE,
5=UNEXPECT
SVFDWAR
NETWORK Network Menu
BMS OCC REQUEST BMS Occupancy Request 0=UNOCC,
1=OCCUPIED,
2=DISABLED
Forcible BMS_OCC
LINKAGE OCC REQ Linkage Occupied Request 0=Un occ,
1=Occupied,
2=Disabled
LNK_OCC
OAT NETWORK VALUE Network OAT Value xxx.x °F OAT_NET
RAT NETWORK VALUE Network Return Air Temp xxx.x °F RAT_NET
SPT NETWORK VAL. Network Space Temp V alue xxx.x °F SPT_NET
OARH NETWORK VAL. Network OARH Value 0 t o 100 % OARH_NET
RARH NETWORK VAL. Network RARH V alue 0 t o 100 % RARH_NET
IAQ NETWORK VALUE Network IAQ Value xxxx ppm IAQ_NET
OAQ NETWORK VALUE Network OAQ V alue xxxx ppm OAQ_NET
OACFM NETWORK VAL Network OACFM Value xxxx cfm OCFM_NET
ZS SENS OR INFO ZS Sensor Information
ZS SPACE TEMP Zone Sensor Temp Out --- 40 to 245 °F ZSZT
ZS SPACE RH Zone Sensor Humidity Out 0 to 100 % ZSSPRH
ZS SPOFFSET ZS Setpoint Offset Output --- 10 to 10 °Fdelta ZSSPTO
ZS OVER TIME LEFT ZS Override time remain 0 to 600 min ZSOTR
ZS TEMPERA TURE ZS Space Temperature
ZS1 TEMPERATRUE Zone Sensor 1 Temp --- 40 to 245 °F ZS1ZT
ZS2 TEMPERATRUE ZS2 Temperature --- 40 to 245 °F ZS2ZT
ZS3 TEMPERATRUE ZS3 Temperature --- 40 to 245 °F ZS3ZT
ZS4 TEMPERATRUE ZS4 Temperature --- 40 to 245 °F ZS4ZT
ZS5 TEMPERATRUE ZS5 Temperature --- 40 to 245 °F ZS5ZT
ZS HUMIDITY ZS Space Humidity
ZS1 HUMIDITY ZS1 Humidity 0 to 100 % ZS1ZHUM
ZS2 HUMIDITY ZS2 Humidity 0 to 100 % ZS2ZHUM
ZS3 HUMIDITY ZS3 Humidity 0 to 100 % ZS3ZHUM
ZS4 HUMIDITY ZS4 Humidity 0 to 100 % ZS4ZHUM
ZS5 HUMIDITY ZS5 Humidity 0 to 100 % ZS5ZHUM
ZS CSP OFFSET ZS Cool Set Point Offset
ZS1 CSP OFFSET ZS1 cool setpoint offset --- 10 to 10 °Fdelta ZS1CSOFF
ZS2 CSP OFFSET ZS2 cool setpoint offset --- 10 to 10 °Fdelta ZS2CSOFF
ZS3 CSP OFFSET ZS3 cool setpoint offset --- 10 to 10 °Fdelta ZS3CSOFF
ZS4 CSP OFFSET ZS4 cool setpoint offset --- 10 to 10 °Fdelta ZS4CSOFF
ZS5 CSP OFFSET ZS5 cool setpoint offset --- 10 to 10 °Fdelta ZS5CSOFF
ZS H SP OFFSET ZS Heat Set Point Offset
ZS1 HSP OFFSET ZS1 Heat Setpoint Offset --- 10 to 10 °Fdelta ZS1HSOFF
ZS2 HSP OFFSET ZS2 Heat Setpoint Offset --- 10 to 10 °Fdelta ZS2HSOFF
ZS3 HSP OFFSET ZS3 Heat Setpoint Offset --- 10 to 10 °Fdelta ZS3HSOFF
ZS4 HSP OFFSET ZS4 Heat Setpoint Offset --- 10 to 10 °Fdelta ZS4HSOFF
ZS5 HSP OFFSET ZS5 Heat Setpoint Offset --- 10 to 10 °Fdelta ZS5HSOFF
ZS OCC TIME OVER ZS Occ Timed Override
ZS1 OCC TIME OVER ZS1 Override time remaining 0 to 600 min ZS1OTR
ZS2 OCC TIME OVER ZS2 Override time remaining 0 to 600 min ZS2OTR
ZS3 OCC TIME OVER ZS3 Override time remaining 0 to 600 min ZS3OTR
ZS4 OCC TIME OVER ZS4 Override time remaining 0 to 600 min ZS4OTR
ZS5 OCC TIME OVER ZS5 Override time remaining 0 to 600 min ZS5OTR