Table 3—Electrical Data—50SD
UNIT
SIZE
V-PH-HZ
VOLTAGE
RANGE
COMPRESSOR OFM IFM
ELECTRIC HEAT
(SINGLE POINT CONNECTION)
POWER SUPPLY
Min Max RLA LRA FLA FLA Nominal Kw
*
FLA MCA
Max Fuse
or
Ckt Bkr
MOCP
024 208/230–1–60 187 253 10.9 54.0 0.9 2.0
-/-
3.8/5.0
7.5/10.0
5.4/7.2
-/-
18.1/20.8
36.1/41.7
26.0/30.0
16.5/16.5
25.1/28.5
47.6/54.6
35.0/40.0
20/20
30/30
50/60
35/40
030 208/230–1–60 187 253 14.0 72.5 0.9 2.0
-/-
3.8/5.0
7.5/10.0
11.3/15.0
5.4/7.2
-/-
18.1/20.8
36.1/41.7
54.2/62.5
26.0/30.0
20.4/20.4
25.1/28.5
47.6/54.6
70.2/80.6
35.0/40.0
25/25
25/30
50/60
35/40
80/90
036 208/230–1–60 187 253 16.0 88.0 0.9 3.1
-/-
3.8/5.0
7.5/10.0
11.3/15.0
5.4/7.2
-/-
18.1/20.8
36.1/41.7
54.2/62.5
26.0/30.0
24.0/24.0
26.4/29.9
49.0/56.0
71.6/82.0
36.4/41.4
30/30
30/30
50/60
40/45
80/90
042 208/230–1–60 187 253 18.4 104.0 0.9 4.1
-/-
3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
5.4/7.2
-/-
18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
26.0/30.0
28.0/28.0
28.0/31.2
50.3/57.2
72.8/83.3
95.4/109.3
37.6/42.6
35/35
35/35
60/60
40/45
80/90
100/110
048 208/230–1–60 187 253 18.3 109.0 1.5 4.1
-/-
3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
5.4/7.2
-/-
18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
26.0/30.0
28.5/28.5
28.5/31.2
50.3/57.2
72.8/83.3
95.4/109.3
37.6/42.6
35/35
35/35
60/60
40/45
80/90
100/110
060 208/230–1–60 187 253 25.0 148.0 1.5 6.2
-/-
3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
5.4/7.2
-/-
18.1/20.8
36.1/41.7
54.2/62.5
72.2/83.3
26.0/30.0
39.0/39.0
39.0/39.0
52.9/59.8
75.4/85.9
98.0/111.9
40.2/45.3
50/50
50/50
60/60
50/50
80/90
100/125
(See legend following Electrical Data charts)
A05108
LEGEND
FLA Full Load Amps
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
RLA Rated Load Amps
NOTES:
1. In compliance with NEC (National Electrical Code) requirements
for multimotor and combination load equipment (refer to NEC
Articles 430 and 440), the overcurrent protective device for the
unit shall be Power Supply fuse. The CGA (Canadian Gas
Association) units may be fuse or circuit breaker.
2. Minimum wire size is based on 60 C copper wire. If other than
60 C wire is used, or if length exceeds wire length in table,
determine size from NEC.
®
Fig. 10—High- and Control-Voltage Connections
C99010
POWER
SUPPLY
FIELD-SUPPLIED
FUSED DISCONNECT
HIGH VOLTAGE
POWER LEADS
(SEE UNIT WIRING
LABEL)
GND
CONTROL BOX
SPLICE BOX
LOW-VOLTAGE
POWER LEADS
(SEE UNIT
WIRING LABEL)
Y
G
R
C
YEL(Y)
GRN(G)
RED(R)
BRN(C)
THERMOSTAT
(TYPICAL)
LEGEND
Field Control-Voltage Wiring
Field High-Voltage Wiring
NOTE: Use blue wire for 3-phase units only.