Loading...
UNIT FALLING HAZARD
Failure to follow this warnig could result to personal injury or
death. Never stand beneath rigged units or lift over people.
Never exceed 200 lbs. per bracket lifting force.
UNIT FALLING HAZARD
Failure to follow this warning could result to personal injury
or death.
Accessory lifting kit is only to be used with Small Packaged
units which have a composite base pan with molded rigging
holds.
INSPECTION
Prior to initial use, and at monthly intervals, all rigging brackets
and straps should be visually inspected for any damage, evidence
Fig. 3—50SD036–060 Unit Dimensions
UNIT ELECTRICAL CHARACTERISTICS
UNIT WEIGHT
UNIT HEIGHT
IN. (MM)
”A”
CENTER OF GRAVITY
IN. (MM)
lb. kg X Y Z
50SD036 208/230-1-60 433 196 42.98 (1092) 21.0 (533) 20.5 (520) 16.6 (422)
50SD042 208/230-1-60 460 209 46.98 (1193) 21.0 (533) 20.5 (520) 17.1 (434)
50SD048 208/230-1-60 480 218 46.98 (1193) 21.0 (533) 20.0 (508) 17.4 (442)
50SD060 208/230-1-60 492 223 46.98 (1193) 21.0 (533) 20.0 (508) 17.6 (447)
A05126
R
E
Q
U
I
R
E
D
C
L
E
A
R
A
N
C
E
F
O
R
O
P
E
R
A
T
I
O
N
A
ND
S
E
R
V
I
C
I
N
G
INCHES [mm]
EVAP. COIL ACCESS SIDE............................................................36.00 [914.0]
POWER ENTRY SIDE....................................................................42.00 [1066.8]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP .......................................................................................48.00 [1219.2]
SIDE OPPOSITE DUCTS ..............................................................36.00 [914.0]
DUCT PANEL .................................................................................12.00 [304.8] *
*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 304.8 [12.00] FROM
WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE.
R
E
Q
U
I
R
E
D
C
L
E
A
R
A
N
C
E
T
O
C
O
M
B
U
S
T
I
B
L
E
M
A
TL
.
INCHES [mm]
TOP OF UNIT...................................................................................14.00 [355.6]
DUCT SIDE OF UNIT.........................................................................2.00 [50.8]
SIDE OPPOSITE DUCTS ................................................................14.00 [355.6]
BOTTOM OF UNIT.............................................................................0.50 [12.7]
N
E
C
.
R
E
Q
U
I
R
E
D
C
L
E
A
R
A
N
C
E
S
.
INCHES [mm]
BETWEEN UNITS, POWER ENTRY SIDE ....................................42.00 [1066.8]
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00 [914.0]
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE.........................42.00 [1066.8]
(
R
e
f
e
r
t
o
M
a
x
i
m
u
m
O
p
e
r
a
t
i
ng
C
l
ea
r
a
n
c
e
s
)
4