EasyManua.ls Logo

Carrier 50SD - Page 16

Carrier 50SD
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 5—Wet Coil Air Delivery (Deduct 10 percent for 208v)*
Horizontal and Downflow Discharge
Unit 50SD024-060
230 VOLT
Unit
Motor
Speed
External Static Pressure (in. wg)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
024
Low
Watts311309304301286————
Cfm935885820757686————
Med
Watts————379357357345327
Cfm————957868769647365
High
Watts——————447435421
Cfm——————970853712
030
Low
Watts311309304301—————
Cfm935885820757—————
Med
Watts 411 405 398 390 379 357 357
Cfm 1195 1155 1100 1028 957 868 769
High
Watts————477467447435
Cfm————1185 1088 970 853
036
Low
Watts 437 433 424 417 403 391 379 362
Cfm 1353 1318 1283 1235 1187 1123 1059 975
Med
Watts 531 516 496 478 459 435
Cfm 1489 1437 1362 1289 1208 1099
High
Watts———————629602
Cfm———————1470 1357
042
Low
Watts 625 606 586 571 550 534 509 483 457
Cfm 1539 1496 1466 1437 1387 1330 1264 1183 1093
Med
Watts 741 715 694 669 645 610 573 544
Cfm 1738 1698 1653 1604 1538 1457 1362 1271
High
Watts—————798772738700
Cfm—————172016481540 1414
048
Low
Watts 627 617 607 584 567 548 528 503
Cfm 1550 1530 1493 1461 1414 1361 1320 1250
Med
Watts 771 755 734 711 690 665 639 607 572
Cfm 1798 1771 1734 1687 1645 1595 1530 1449 1355
High
Watts 908 887 858 827 804 767 748
Cfm 2000 1994 1876 1811 1735 1647 1555
060
Low
Watts 786 769 754 736 722 705 684 658
Cfm 2027 1960 1901 1821 1759 1693 1616 1513
Med
Watts 873 849 833 815 798 782 763 748
Cfm 2095 2026 1962 1887 1817 1748 1679 1583
High
Watts 1012 993 981 963 948 927 904 886
Cfm 2184 2109 2036 1963 1886 1812 1729 1647
* Air delivery values are based on operating voltage of 230v wet coil, without filter or electric heater. Deduct filter and electric heater pressure drops to obtain static
pressure available for ducting.
NOTES:
1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at airflows below
this point.
2. Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended.
16

Other manuals for Carrier 50SD

Related product manuals