Base unit dimensions 50TFQ004-007
OPTIONAL CONVENIENCE OUTLET
OPTIONAL NON-FUSED
DISCONNECT LOCATION
UNIT
STD UNIT
WEIGHT
DURABLADE
ECON WEIGHT
ECONOMI$ER
WEIGHT
(A)
CORNER WEIGHT
(B)
CORNER WEIGHT
(C)
CORNER WEIGHT
(D)
CORNER WEIGHT
Lbs Kg Lbs Kg Lbs Kg Lbs Kg Lbs Kg Lbs Kg Lbs Kg
50TFQ004
500 227 34 15.4 47 21.3 125 57 120 54 125 57 130 59
50TFQ005
520 236 34 15.4 47 21.3 130 59 125 57 130 59 135 61
50TFQ006
550 249 34 15.4 47 21.3 138 63 132 60 138 62 142 64
50TFQ007
590 268 34 15.4 47 21.3 148 68 142 64 148 67 152 69
CONNECTION SIZES
A
1
3
/
8
Dia. [35] Field Power Supply Hole
B
2
Dia. [51] Power Supply Knockout
C
1
3
/
4
Dia. [44] Charging Port Hole
D
7
/
8
Dia. [22] Field Control Wiring Hole
E
3
/
4
″−
14 NPT Condensate Drain
F
2
1
/
2
Dia. [64] Power Supply Knockout
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Center of gravity.
3. Direction of airflow.
4. Ductwork to be attached to accessory roof curb only.
5. Minimum clearance (local codes or jurisdiction may prevail):
a. Bottom to combustible surfaces (when not using curb) 0 in., on horizontal discharge units with electric
heat 1 in. clearance to ductwork for 1 ft.
b. Outdoor coil, for proper airflow, 36 in. one side, 12 in. the other. The side getting the greater clearance is
optional.
c. Overhead, 60 in. to assure proper outdoor fan operation.
d. Between units, control box side, 42 in. per NEC (National Electrical Code).
e. Between unit and ungrounded surfaces, control box side, 36 in. per NEC.
f. Between unit and block or concrete walls and other grounded surfaces, control box side, 42 in. per NEC.
g. Horizontal supply and return end, 0 inches.
6. With the exception of the clearance for the outdoor coil and combustibles as stated in Notes 5a, b, and c, a
removable fence or barricade requires no clearance.
7. Units may be installed on combustible floors made from wood or class A, B, or C roof covering material.
8. The vertical center of gravity is 1
-6
1/
2
[470] up from the bottom of the base rail.
BOTTOM POWER CHART, THESE HOLES
REQD FOR USE WITH ACCESSORY PACKAGES
CRBTMPWR001A00 (
1
/
2
,
3
/
4
)
OR
CRBTMPWR002A00 (
1
/
2
, 1
1
/
4
)
*Select either
3
/
4
in. or 1
1
/
4
for power, depending on wire size.
THREADED
CONDUIT
SIZE
WIRE
USE
REQD HOLE
SIZES (Max.)
1
/
2
3
/
4
1
1
/
4
24 V
Power*
Power*
7
/
8
[22.2]
1
1
/
8
[28.4]
1
3
/
4
[44.4]