EasyManua.ls Logo

Carrier 50TFQ004-007 - Defrost (50 TFQ004-007); Defrost (50 TFQ008-012); Apollo Communicating Control Wiring Schematic

Carrier 50TFQ004-007
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
67
Defrost (50TFQ004-007) — As frost builds up on the
outdoor coil, the coil temperature drops below 28 F. When
this outdoor-coil temperature drop is sensed by the defrost
thermostat (DFT) and the defrost timer is at the end of a
timed period (adjustable at 30, 50, or 90 minutes), the unit
operates in a defrost cycle controlled by the defrost timer
and thermostat. During this cycle, the reversing valve sole-
noid (RVS) is energized and the outdoor fan shuts off. The
electric heaters (if installed) will be energized.
The unit continues to defrost until the coil temperature
as measured by DFT reaches 65 F, or the duration of de-
frost cycle completes a 10-minute period.
At the end of the defrost cycle, the electric heaters (if in-
stalled) and the reversing valve will be deenergized, and the
outdoor-fan motor will be energized. The unit will now op-
erate in the Heating mode.
If the thermostat is satisfied during a defrost cycle, the
unit will continue in the Defrost mode until the time or tem-
perature constraints are satisfied.
Defrost (50TFQ008-012) — When the temperature of
the outdoor coil drops below 28 F as sensed by the defrost
thermostat (DFT2) and the defrost timer is at the end of a
timed period (adjustable at 30, 50, or 90 minutes), revers-
ing valve solenoids (RVS1 and RVS2) are energized and
the OFC is deenergized. This switches the position of the
reversing valves and shuts off the outdoor fan. The electric
heaters (if installed) will be energized.
The unit continues to defrost until the coil temperature
as measured by DFT2 reaches 65 F, or the duration of de-
frost cycle completes a 10-minute period.
During the Defrost mode, if circuit 1 defrosts first, RVS1
will oscillate between Heating and Cooling modes until the
Defrost mode is complete.
At the end of the defrost cycle, the electric heaters (if in-
stalled) will be deenergized; the reversing valves switch and
the outdoor-fan motor will be energized. The unit will now
operate in the Heating mode.
If the space thermostat is satisfied during a defrost cycle,
the unit will continue in the Defrost mode until the time or
temperature constraints are satisfied.
APOLLO COMMUNICATING CONTROL WIRING SCHEMATIC,
50TFQ004-007 UNITS
LEGEND
C
Contactor
NC
Normally Closed
CHAS
Ground
NO
Normally Open
COM
Common
OAT
Outdoor-Air Thermostat
DX
Direct Expansion
SAT
Saturated-Air Temperature
ECON
Economizer
VVT
Variable Volume/Variable
GND
Ground Temperature
HT
Heat

Table of Contents

Related product manuals