INSTALLATION
1. Remove unit from shipping carton. Leave top shipping skid on
the unit as a spreader bar to prevent the rigging straps from
damaging the unit. If the wood skid is not available, use a
spreader bar of sufficient length to protect unit from damage.
2. Position the lifting bracket assembly around the base of the
unit. Be sure the strap does not twist.
3. Place each of the 4 metal lifting brackets into the rigging holds
in the composite unit base.
4. Thread lifting bracket strapping around bottom perimeter of
unit as follows:
a. Open lever of tension buckle (ratchet type).
b. Feed strapping through tension buckle as shown in Fig. 8.
c. Pull strapping through tension buckle unit taut.
Fig. 3—50XZ 042-060 Unit Dimensions
UNIT ELECTRICAL CHARACTERISTICS
UNIT WEIGHT
UNIT HEIGHT
IN. (MM)
”A”
CENTER OF GRAVITY
IN. (MM)
lb kg X Y Z
50XZ042 Not Available At This Time
50XZ048 208/230-1-60, 208/230-3-60 463 210 44.98 (1142.5) 19.5 (495.3) 17.6 (447.6) 18.0 (457.2)
50XZ060 208/230-1-60, 208/230-3-60 499 226 46.98 (1193.3) 21.0 (533.4) 20.0 (508.0) 17.6 (442.0)