EasyManua.ls Logo

Carrier 50YDV - Unit Operating Conditions

Carrier 50YDV
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
41
Residential Packaged Units - 60Hz Puron
®
Rev.: 4 Jan., 2012
Unit Operating Conditions
Table 12: GT-PG Series Typical Unit Operating Pressures and Temperatures: Continued
070 Full Load Cooling - without HWG active Full Load Heating - without HWG active
Entering
Water
Temp °F
Water
Flow
GPM/ton
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Superheat Subcooling
Water
Temp
Rise
°F
Air Temp
Drop °F
DB
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Superheat Subcooling
Water
Temp Drop
°F
Air Temp
Rise °F
DB
30*
1.5
2.25
3
110-120
109-119
107-117
177-197
162-182
147-167
36-41
37-42
38-43
15-20
13-18
11-16
20.2-22.2
15-17
9.7-11.7
21-27
21-27
22-28
61-71
65-75
68-78
290-310
292-312
296-316
12-18
12-18
12-18
9-14
10-15
10-15
8-10
6-8
4-6
19-25
20-26
21-27
50
1.5
2.25
3
128-138
128-138
127-137
246-266
228-248
210-230
18-23
19-24
20-25
11-16
9-14
6-11
21-23
15.6-17.6
10.2-12.2
22-28
23-29
24-30
88-98
96-106
105-115
320-340
330-350
338-358
11-17
11-17
11-17
13-18
11-16
9-14
11.7-13.7
9-11
6-8
26-32
27-33
29-35
70
1.5
2.25
3
134-144
133-143
131-141
305-325
289-309
273-293
9-14
9-14
9-14
11-16
9-14
6-11
20.8-22.8
15.4-17.4
10-12
23-29
23-29
23-29
118-128
130-140
141-151
355-375
368-388
380-400
10-16
12-18
15-21
14-19
13-18
11-16
15.2-17.2
11.7-13.7
8-10
33-39
35-41
37-43
90
1.5
2.25
3
140-150
139-149
138-148
390-410
373-393
355-375
10-15
10-15
10-15
11-16
9-14
6-11
19.6-21.6
14.5-16.5
9.3-11.3
22-28
22-28
22-28
158-168
168-178
178-188
401-421
412-432
423-443
9-15
10-16
12-18
13-18
12-17
12-17
19.5-21.5
14.8-16.8
10-12
41-47
43-49
45-51
110
1.5
2.25
3
144-154
143-153
142-152
488-508
468-488
448-468
10-15
10-15
9-14
9-14
6-11
5-10
18.4-20.4
13.6-15.6
8.8-10.8
20-27
20-27
20-27
*Based on 15% Methanol antifreeze solution