Residential Packaged Units - 60Hz Puron
®
Rev.: 4 Jan., 2012
12
Ground-Loop Heat Pump Applications
antifreeze solution is used in most areas to prevent freezing. 
All air and debris must be removed from the earth loop piping 
before operation. Flush the loop with a high volume of water 
at a minimum velocity of 2 fps (0.6 m/s) in all piping. The 
steps below must be followed for proper fl ushing. 
1.  Fill loop with water from a garden hose through the fl ush 
cart before using the fl ush cart pump to insure an even fi ll. 
2.  Once full, the fl ushing process can begin. Do not allow 
the water level in the fl ush cart tank to drop below the 
pump inlet line to avoid air being pumped back out to 
the earth loop. 
3.  Try to maintain a fl uid level in the tank above the return 
tee so that air cannot be continuously mixed back into 
the fl uid. Surges of 50 psi (345 kPa) can be used to help 
purge air pockets by simply shutting off the return valve 
going into the fl ush cart reservoir. This “dead heads” the 
pump to 50 psi (345 kPa). To purge, dead head the pump 
until maximum pumping pressure is reached. Open the 
return valve and a pressure surge will be sent through the 
loop to help purge air pockets from the piping system. 
4.  Notice the drop in fl uid level in the fl ush cart tank when 
the return valve is shut off. If air is adequately purged from 
the system, the level will drop only 1-2 inches (2.5 - 5 cm) 
in a 10” (25 cm) diameter PVC fl ush tank (about a half 
gallon [2.3 liters]), since liquids are incompressible. If the 
level drops more than this, fl ushing should continue since 
air is still being compressed in the loop fl uid. Perform the 
“dead head” procedure a number of times.Note: This 
fl uid level drop is your only indication of air in the loop.
5.  Consult Whole House Dehumidifi cation AOM 
for fl ushing instructions for units equipped with 
Whole House Dehumidifi cation Whole House 
Dehumidifi cation option.
Antifreeze may be added before, during or after the fl ushing 
procedure. However, depending upon which time is chosen, 
antifreeze could be wasted when emptying the fl ush cart 
tank. See antifreeze section for more details.
Loop static pressure will fl uctuate with the seasons. 
Pressures will be higher in the winter months than during 
the cooling season. This fl uctuation is normal and should 
be considered when charging the system initially. Run the 
unit in either heating or cooling for a number of minutes to 
condition the loop to a homogenous temperature. This is 
a good time for tool cleanup, piping insulation, etc. Then, 
perform fi nal fl ush and pressurize the loop to a static 
pressure of 50-75 psi [345-517 kPa] (winter) or 35-40 psi 
[241-276 kPa] (summer). After pressurization, be sure to 
loosen the plug at the end of the Grundfos loop pump 
motor(s) to allow trapped air to be discharged and to insure 
the motor housing has been fl ooded. This is not required 
for Taco circulators. Insure that the Flow Controller provides 
adequate fl ow through the unit by checking pressure drop 
across the heat exchanger and compare to the pressure 
drop tables at the back of the manual.
Antifreeze
In areas where minimum entering loop temperatures drop 
below 40°F [5°C] or where piping will be routed through 
areas subject to freezing, antifreeze is required. Alcohols 
and glycols are commonly used as antifreeze; however your 
local sales manager should be consulted for the antifreeze 
best suited to your area. Low temperature protection should 
be maintained to 15°F [9°C] below the lowest expected 
entering loop temperature. For example, if 30°F [-1°C] is 
the minimum expected entering loop temperature, the 
leaving loop temperature would be 25 to 22°F [-4 to -6°C] 
and low temperature protection should be at 15°F [-10°C].  
Calculation is as follows:
30°F - 15°F = 15°F [-1°C - 9°C = -10°C]. 
All alcohols should be premixed and pumped from a 
reservoir outside of the building when possible or introduced 
under the water level to prevent fumes. Calculate the 
total volume of fl uid in the piping system. Then use the 
percentage by volume shown in Table 2 for the amount 
of antifreeze needed. Antifreeze concentration should be 
checked from a well mixed sample using a hydrometer to 
measure specifi c gravity.
Table 1: Approximate Fluid Volume (gal.) per 100' of Pipe
Fluid Volume (gal [liters] per 100’ [30 meters) Pipe)
Pipe Size Volume (gal) [liters]
Copper
1” 4.1 [15.3]
1.25” 6.4 [23.8]
2.5” 9.2 [34.3]
Rubber Hose  1” 3.9 [14.6]
Polyethylene
3/4” IPS SDR11 2.8 [10.4]
1” iPS SDR11 4.5 [16.7]
1.25” IPS SDR11 8.0 [29.8]
1.5” IPS SDR11 10.9 [40.7]
2” IPS SDR11 18.0 [67.0]
1.25” IPS SCH40 8.3 [30.9]
1.5” IPS SCH40 10.9 [40.7]
2” IPS SCH40 17.0 [63.4]
Unit Heat Exchanger Typical 1.0 [3.8]
Flush Cart Tank
10” Dia x 3ft tall
[254mm x 91.4cm tall]
10 [37.9]
Low Water Temperature Cutout Setting - CXM Control
When antifreeze is selected, the FP1 jumper (JW3) should 
be clipped to select the low temperature (antifreeze 10°F 
[-12.2°C]) set point and avoid nuisance faults (see “Low 
Water Temperature Cutout Selection” in this manual). Note:  
Low water temperature operation requires extended range 
equipment.