Residential Packaged Units - 60Hz Puron
®
Rev.: 4 Jan., 2012
22
Electrical - Low Voltage Wiring
Figure 20: Accessory Wiring
Figure 21: AVM Valve Wiring
C
C
Thermostat
Y1
1
2
3
Y1
AVM
Taco Valve
Heater Switch
Figure 22: Taco SBV Valve Wiring
From Water Source
IN
OUT
NOTE:  Shut-off valves, strainers and
other required components not shown.
Solenoid
Valve
Flow
Regulator
To Discharge
Stage 1
Stage 2
Figure 23: Two-Stage Piping
ccessor
 
onnection
Water Solenoid Valves 
An external solenoid valve(s) should be used on ground 
water installations to shut off fl ow to the unit when the 
compressor is not operating. A slow closing valve may be 
required to help reduce water hammer. Figure 20 shows 
typical wiring for a 24VAC external solenoid valve. Figures 
21 and 22 illustrate typical slow closing water control valve 
wiring for Taco 500 series (ClimateMaster P/N AVM…) 
and Taco SBV series valves. Slow closing valves take 
approximately 60 seconds to open (very little water will fl ow 
before 45 seconds). Once fully open, an end switch allows 
the compressor to be energized. Only relay or triac based 
electronic thermostats should be used with slow closing 
valves. When wired as shown, the slow closing valve will 
operate properly with the following notations:
1.  The valve will remain open during a unit lockout.
2.  The valve will draw approximately 25-35 VA through the 
“Y” signal of the thermostat. 
  Note: This valve can overheat the anticipator of an 
electromechanical thermostat. Therefore, only relay or 
triac based thermostats should be used.
Two-stage Units
Tranquility 27™ (TT) two-stage units should be designed with 
two parallel valves for ground water applications to limit water 
use during fi rst stage operation. For example, at 1.5 gpm/
ton [2.0 l/m per kW], an 049 unit requires 6 gpm [23 l/m] for 
full load (2nd stage) operation, but only 4 gpm [15 l/m] during 
1st stage operation. Since the unit will operate on fi rst stage 
80-90% of the time, signifi cant water savings can be realized 
by using two parallel solenoid valves with two fl ow regulators. 
In the example above, stage one solenoid would be installed 
with a 4 gpm [15 l/m] fl ow regulator on the outlet, while stage 
two would utilize a 2 gpm [8 l/m] fl ow regulator. When stage 
one is operating, the second solenoid valve will be closed. 
When stage two is operating, both valves will be open, 
allowing full load fl ow rate. 
Figure 23 illustrates piping for two-stage solenoid valves. 
Review fi gures 20-22 for wiring of stage one valve. Stage two 
valve should be wired between terminal “Y2” (ECM board) 
and terminal “C.” 
Note: When EWT is below 50°F [10°C], a minimum of 2 
gpm per ton (2.6 l/m per kW) is required.
Accessory Connections
A terminal paralleling the compressor contactor coil has 
been provided on the CXM control. Terminal “A” is designed 
to control accessory devices, such as water valves. Note: 
This terminal should be used only with 24 Volt signals 
and not line voltage. Terminal “A” is energized with the 
compressor contactor. See Figure 20 or the specifi c unit 
wiring diagram for details.