To Previous Page IconTo Previous Page
Loading...
8
Table 3—Required Subcooling
REQUIRED SUBCOOLING °F(°C)
Model Size
Outdoor Ambient Temperature
75 (24) 82 (28) 85 (29) 95 (35) 105 (41)
048 17.5 (9.7) 17 (9.4) 16.5 (9.2) 16 (8.9) 14 (7.8)
060 21 (11.7) 20.5 (1 1.4) 20 (11.1) 19 (10.6) 16 (8.9)
Table 4—Required Liquid Line Temperature
REQUIRED LIQUID LINE TEMPERATURE FOR A SPECIFIC SUBCOO LING (R--22)
Pressure (kPa)
Required Subcooling (°F)
Pressure (kPa)
Required Subcooling (°F)
5 10 15 20 3 6 8 11
134 71 66 61 56 924 24 22 19 16
141 74 69 64 59 972 26 23 21 18
156 80 75 70 65 1075 30 27 24 21
163 83 78 73 68 1124 31 28 26 23
170 86 81 76 71 1172 33 30 27 24
177 89 84 79 74 1220 34 31 29 26
184 91 86 81 76 1268 36 33 30 27
191 94 89 84 79 1317 37 34 31 29
198 96 91 86 81 1365 38 36 33 30
205 98 93 88 83 1413 40 37 34 31
213 101 96 91 86 1468 41 38 36 33
221 104 99 94 89 1524 43 40 37 34
229 106 101 96 91 1579 44 41 38 36
237 108 103 98 93 1634 45 42 40 37
245 111 106 101 96 1689 47 44 41 38
253 113 108 103 98 1744 48 45 42 40
262 116 111 106 101 1806 49 46 44 41
271 118 113 108 103 1868 51 48 45 42
280 121 116 111 106 1930 52 49 46 44
289 123 118 113 108 1992 53 51 48 45
298 125 120 115 110 2054 55 52 49 46
307 128 123 118 113 2116 56 53 50 48
317 130 125 120 115 2185 57 54 52 49
327 132 127 122 117 2254 59 56 53 50
337 135 130 125 120 2323 60 57 54 52
347 137 132 127 122 2392 61 58 56 53
357 139 134 129 124 2461 62 60 57 54
367 142 137 132 127 2530 64 61 58 55
280 121 116 111 106 1930 52 49 46 44
289 123 118 113 108 1992 53 51 48 45
298 125 120 115 110 2054 55 52 49 46
307 128 123 118 113 2116 56 53 50 48
317 130 125 120 115 2185 57 54 52 49
327 132 127 122 117 2254 59 56 53 50
337 135 130 125 120 2323 60 57 54 52
347 137 132 127 122 2392 61 58 56 53
357 139 134 129 124 2461 62 60 57 54
367 142 137 132 127 2530 64 61 58 55
Step 3—Refrigerant Charge
Refrigerant Charge Amount of refrigerant charge is listed on unit
nameplate and in Table 1. Refer to Carrier Refrigerant Service
Techniques Manual, Refrigerants section. Unit panels must be in
place when unit is operating during charging procedure. Unit must
operate a minimum of 15 minutes before checking charge.
NO CHARGE
Refer to Carrier Refrigerant Service Techniques. Use standard
evacuating techniques. After evacuating system, weigh in the
specified amount of refrigerant (refer to Table 1).
LOW CHARGE COOLING
024--042 units:
1. Measure suction line pressure by attaching a gauge to the
service port.
2. Measure the suction line temperature by attaching a
temperature sensing device to it.
3. Insulate the temperature sensing device so that the outdoor
ambient doesn’t affect the reading.
4. Locate the measured suction line pressure in the top row of
Table 7 and the measured outdoor ambient temperature in
the left column of the table. Based on the two values,
determine the required suction line temperature.
5. If the measured suction line temperature is greater than the
tabulated temperature, add charge in the system.
048 and 060 units:
1. Measure discharge line pressure by attaching a gauge to the
service port.
2. Measure the liquid line temperature by attaching a
temperature sensing device to it.
50ZPA