Important -- Before you Begin
When using unoccupied modes, Auto fan speed must be
selected. Manual fan speed should not be used for unoc-
cupied operation. Auto Fan speed must be used to pre-
vent the system from entering the coil freeze protection
cycle or in heating, the high-pressure protection cycle.
(See Advanced Set-Up Section for fan speed selection.)
If different heating and/or cooling temperature set points
are desired Monday through Friday, at different times of
the day, two occupied periods must be programmed. To
adjust set points and times for the two occupied periods:
If the space to be controlled should have a designated
temperature from 7:00 a.m. to 5:00 p.m. Monday through
Friday and for the remainder of the day have an alternate
or setback temperature set point set to stop at 5:00 p.m.,
program the occupied (2) mode at 12:00 a.m. to
12:00 a.m. at the alternate temperature set point.
NOTE: If one occupied period starts and stops within an-
other occupied period the lower occupied number has
priority.
If additional setback is desired for Saturday and Sunday,
program occupied (1) from 12:00 a.m. to 12:00 a.m. for
both Saturday and Sunday at the desired temperature.
Press the Mode button While holding the Mode Button,
press the Up button for 2 seconds to enter time period
MODE _ programming¸
(_ Select the maximum number
of occupied periods to be
) used on any one day.
Typically 1.
(1,2 or 3)
set point for occupied 1. COOL
_/) (35 to 99 F)
(_ Adiust the heating
(_ set point for occupied 1.
(35 to 99 F)
HEAT
7?
Adjust t he cooling _
set pointforunoccupied COOL
periods.
(35 to 99 F)
Select the day for M°TuWeThFr
Occupied 1.
X /
Adiust the start time
for occupied 1
............. J
\, 9
Adiust the stop time
for occupied 1.
/
On
Select Occupied I to run
on this day (On), ol not to
lun this day (Off).
Off
ON
To exit programming press the Mode button.
While holding Mode, press the Up button.
//%x
Programming Notes
If only one Occupied period is selected in Step 1 on
this page, Occupied 2 and 3 programming steps are
skipped. Further, if only 2 occupied periods are
selected, Occupied 3 programming steps are
skipped.
Heat and Cool set points for Occupied 1 are the
same for every day of the week. Heat and Cool set
points for Occupied 2 and 3 can be adjusted differ-
ently for weekdays and weekends, if desired.
The Unoccupied settings take effect at all times
when: (1) the program is on and (2) the current time
is outside a preset occupied period. For this reason
start and stop times are not necessary for
unoccupied.
If the same start and stop times are programmed in
for an occupied period, then it will run 24 hours.
If one occupied period starts and stops within
another occupied period the lower occupied num-
ber has priority. For example: If Occupied 3 is pro-
grammed to be "on" 24 hours, and Occupied 2 is
programmed to run that day, then Occupied 2 set-
tings will take over from Occupied 3 between
Occupied 2 start and stop times.
Adjust the heating
set point for unoccupied
) periods.
(0F,35 to 99 F)
COOL
HEAT
Page 3

Other manuals for Carrier 53DFST2-NP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier 53DFST2-NP and is the answer not in the manual?

Carrier 53DFST2-NP Specifications

General IconGeneral
BrandCarrier
Model53DFST2-NP
CategoryThermostat
LanguageEnglish

Related product manuals