6
 
7. Replace control access door. (See Fig. 16.)
 
16
17 18
 
8. Turn ON the electrical supply to the furnace and wait 1 
minute. (See Fig. 17.)
9. Open the external manual gas valve. (See Fig. 18.)
10. Set the room thermostat to a temperature slightly 
above the room temperature. This will automatically 
signal the furnace to start. 
11. When the furnace receives the start signal, the hot surface 
ignitor at the main burners is automatically heated for 15 
to 20 sec. When the microprocessor control verifies that 
there is sufficient heat to ignite, the gas valve permits gas 
to flow to the main burners. After ignition and a time delay 
of about 35 sec, the furnace blower will start. Variable-
capacity furnaces start at low speed until the control 
makes the necessary adjustments to operate the blower at 
either the low- or high-fire speed.
 
NOTE:
 
 If the burners fail to ignite after 4 attempts, the fur-
nace control system will lock out. If lockout occurs, main 
burners fail to light, or blower does not come on, shut down 
the furnace and call your dealer for service.
12. Set your thermostat to the temperature that satisfies 
your comfort requirements. SUGGESTION: Setting 
the thermostat back a few degrees—and compensating 
for the difference with warmer clothing—can make a big 
difference in your fuel consumption on extremely cold 
days. The few degrees at the top of your thermostat “com-
fort level’’ are the most costly degrees to obtain.
When the room temperature drops below the temperature 
selected on the thermostat, the furnace will switch on auto-
matically. When the room temperature reaches the degree 
selected on the thermostat, the furnace will be  switched off 
automatically.
Some thermostats have a “FAN’’ mode with 2 selections: 
AUTO and ON. When set on AUTO, the furnace blower 
cycles on and off, controlled by the thermostat. In the ON 
mode, the furnace blower runs continuously. This keeps the 
temperature level in your home more evenly balanced. It also 
continuously filters the indoor air.
 
SHUTTING DOWN YOUR FURNACE
 
Should you ever need to shut down your furnace for service 
or maintenance, you will need to turn the furnace off. The 
following procedures must be followed:
1. Set your room thermostat to the lowest temperature 
setting. (See Fig. 19.)
2. Close the external manual gas valve (See Fig. 9.) 
3. Turn off electrical supply to the furnace. (See Fig. 20.)
 
19
 
4. Remove main furnace door. (See Fig. 11.)
5. Turn the control knob or switch on the gas valve to the 
OFF position. (See Fig. 21 or 22.)
6. Replace the control access door. (See Fig. 16.)
7. If the furnace is being shut down because of a malfunc-
tion, call your dealer as soon as possible.
 
PERFORMING ROUTINE 
MAINTENANCE
 
With proper maintenance and care, your furnace will operate 
economically and dependably. Instructions for basic mainte-
nance are found on this and the following pages. However, 
before beginning maintenance, follow these safety precautions:
 
                       20
O
P
E
N
 
CAUTION
 
Furnace is not to be installed, operated, and then
turned off and left turned off in an unoccupied
structure during winter. (See winterizing proce-
dures in maintenance section).
®
!