APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
General Parameters
LEGEND
*Default value is shown only if configurable in this table.
†0 = OFF
1 = CTLTEST
2 = PUMPDOWN
3 = LOCKOUT
4 = RECYCLE
5 = TRIPOUT
6 = TIMEOUT
7 = PRESTART
8 = STARTUP
9 = AUTORST
10 = RAMPING
11 = RUNNING
12 = OVERRIDE
13 = DEMAND
14 = SHUTDOWN
15 = FREECOOL
16 = CONDFLSH
**RW from network.
CCN TABLE NAME: GENUNIT
PIC 5 PATH: Main Menu General Parameters
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Control Mode
0 = Local, 1 = Network
2 = Remote, 3 = Local Sched
ctl_mode
0 to 3 RO
2 Compressor1 Run Status cm_stas1 0 to 16† RO
3 Deter Start Stop Command stop/start RO
4 Network: Cmd Start/Stop CHIL_S_S NO/YES RW**
5 Network:Cmd Occupied CHIL_OCC NO/YES RW**
6 Cooling / Heating Select HC_SEL COOL/HEAT COOL RW
7 Control Point CTRL_PNT 10.0 to 160.0 °F RW**
8 Control Point Reset reset –30.00 to 30.00 °F RO
9 Actual Setpoint setpoint 10.0 to 150.0 °F RO
10 Percent Load Current AMPS_P 0.0 to 999.0 % RO
11 Motor Percent Kilowatts KW_P 0 to 100 % RO
12 Actual Demand Limit DEM_LIM 10.0 to 100.0 100 % RW**
13 Emergency Stop EMSTOP NO/YES 0 RW**
14 Chiller State Number ch_state 0 to 500 RO
15 Local Schedule Occupied oc_occ NO/YES RO
16 Ice Schedule Occupied ice_occ NO/YES RO
17 MS Start Stop Command ms_stsp STOP/START RO
18 Remote Reset Alarm REM_RST NO/YES RO
19 Stop Override STP_OVER NO/YES NO RW
20 Start Free Cooling FC_START NO/YES NO RW
21 Start Condenser Flush CF_START NO/YES NO RW
RO Read Only
RW Read/Write