71
APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
Master Slave Configuration
Prognostics Config
Reset Configuration
LEGEND *Default value is shown only if configurable in this table.
CCN TABLE NAME: CONF_MS
PIC 5 PATH: Main Menu Configuration Menu Master Slave Config
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Slave Address slv_addr 1 to 236 2 RW
2 Master/Slave Select
0=Disable, 1=Master, 2=Slave
msl_sel 0 to 2 0 RW
3 Chiller Connection Type
0=Parallel, 1=Series
ms_type 0 to 1 0 RW
4 Middle Sensor Option mids_opt YES/NO YES RW
5 Master Lead/Lag Select
0=Lead change to Lag Once Failed
1=Runtime Balance
lead_sel 0 to 1 0 RW
6 Series Counter Flow serct_fl YES/NO NO RW
7 Master per Capacity ms_per 25 to 75 50 % RW
8 LAG Shutdown Threshold lag_shut 25 to 75 50 % RW
9 Prestart Fault Time pref_tim 2 to 30 5 min RW
10 Lead Unload Threshold 50 to 100 100 % RW
11 Lead/Lag Balance Delta ll_bal_d 40 to 400 168 hr RW
12 Lag Start Time lstr_tim 2 to 30 10 min RW
13 Lag Stop Time lstp_tim 2 to 30 10 min RW
14 Lead Pulldown Time lead_pul 0 to 60 0 min RW
15 Lag Minimum Run Time lag_mini 0 to 150 0 min RW
16 Lag Run Delta T lagrundt 0 to 10.0 3.0 ^F RW
17 Lag Off Delta T lagoffdt 0 to 10.0 1.8 ^F RW
CCN TABLE NAME: CONF_PRG
PIC 5 PATH: Main Menu Configuration Menu Prognostics Config
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Prog Function Enable prog_en YES/NO NO RW
2 Oil Change Done oilch_cm YES/NO YES RW
3 Oil Filter Change Done oilfc_cm YES/NO YES RW
4 Trans Calibration Done tracl_cm YES/NO YES RW
5 Refrigerant Charge Done refch_cm YES/NO YES RW
6 Oil Filter PD Threshold oilfl_th –6.7 to 420 10 psig RW
7 Oil Lub Expire Time oilch_nt 1000.0 to 8000.0 2000.0 hr RW
8 Oil Storage Expire Time oilst_nt 5000.0 to 15000.0 8640 hr RW
9 Trans Calib Threshold refgc_th 0 to 5 2 psig RW
10 Low Charge Cond Approach rch_cath 20 to 40 20 °F RW
11 Evap Design Approach ep_dgap 0 to 10 3 °F RW
12 Bearing Degradation beart_th 100 to 230 200 °F RW
CCN TABLE NAME: RESETCFG
PIC 5 PATH: Main Menu Configuration Menu Reset Configuration
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Temp Reset Type
0 = No, 1 = 4 to 20 mA
2 = Remote Temp, 3 = Water DT [delta
temperature]
res_sel 0 to 3 0 RW
2 Degrees Reset At 20 mA der_20ma –30.0 to 30.0 10.0 °F RW
3 Maximum Deg Temp Reset deg_rset –30.0 to 30.0 10.0 °F RW
4 Remote Temp Full Reset remtm_fu –40.0 to 245.0 65.0 °F RW
5 Remote Temp No Reset remtm_no –40.0 to 245.0 85.0 °F RW
6 Deg Reset Water DT Full drwdt_fu –30.0 to 30.0 10.0 °F RW
7 Controlled DT Full Reset ctldt_fu 0.0 to 15.0 0.0 °F RW
8 Controlled DT No Reset ctldt_no 0.0 to 15.0 10.0 °F RW
RW — Read/Write