APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
Maintenance Others
LEGEND *Default value is shown only if configurable in this table.
CCN TABLE NAME: MAIOTHER
PIC 5 PATH: Main Menu Maintenance Menu Maintenance Others
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 5V Sensor Power Monitor tran_v V RO
2 Evap Pres Trans Volts evapp_v V RO
3 Cond Pres Trans Volts condp_v V RO
4 Econ Pres Trans Volts econp_v V RO
5 Diffuser Pres Tran Volts diffp_v V RO
6 Oil Sump Pres Tran Volts opsmp_v V RO
7 Oil Sup Pres Trans Volts opdis_v V RO
8 Evap Enter Water Volts evewp_v V RO
9 Evap Leave Water Volts evlwp_v V RO
10 Cond Enter Water Volts cdewp_v V RO
11 Cond Leave Water Volts cdlwp_v V RO
12 Last Cond Pump Run Time last_cpt RO
13 Prestart Check Status pre_chck NO/YES RO
14 GV1 Pos at Startup OK gvpos_ok NO/YES RO
15 OIL PD at Startup OK oilpd_ok NO/YES RO
16 ECV Pos at Startup OK hgbp_ok NO/YES RO
17 Damper Pos at Startup OK dmp_ok NO/YES RO
18 Oil Pump Req Oil Heater op_heat NO/YES RO
19 Oil Pump Req Prestart op_prest NO/YES RO
20 Oil Pump Req Startup op_start NO/YES RO
21 Oil Pump Req Shutdown op_shut NO/YES RO
22 Oil Pump Req Swift Rst op_srst NO/YES RO
23 Evap Pump Req Startup ep_start NO/YES RO
24 Evap Pump Req Diagnostic ep_diag NO/YES RO
25 Evap Pump Req Frozen ep_freze NO/YES RO
26 Evap Pump Req Shutdown ep_shut NO/YES RO
27 Evap Pump Req Pumpdown ep_pdown NO/YES RO
28 Cond Pump Req Prestart cp_prest NO/YES RO
29 Cond Pump Req Startup cp_start NO/YES RO
30 Cond Pump Req Override cp_overr NO/YES RO
31 Cond Pump Req Shutdown cp_shut NO/YES RO
32 Cond Pump Req Tower cp_tower NO/YES RO
33 Cond Pump Req Diagnostic co_diag NO/YES RO
34 Cond Pump Req Frozen cp_freze NO/YES RO
35 Cond Pump Req Pumpdown cp_pdown NO/YES RO
36 Capacity Inhibit Ramping cap_inhr NO/YES RO
37 Capacity Inhibit Demand cap_inhd NO/YES RO
38 Capacity Decrease Demand cap_decd NO/YES RO
39 Guide Vane Inh Surge gv1_inhs NO/YES RO
40 Capacity Decrease Surge cap_decs NO/YES RO
41 Capacity Inh Low SST capinhst NO/YES RO
42 Capacity Dec Low SST capdecst NO/YES RO
43 Capacity Inh Cond Pres capinhcp NO/YES RO
44 Capacity Dec Cond Pres capdeccp NO/YES RO
45 Capacity Inh Motor Temp capinhmt NO/YES RO
46 Capacity Dec Motor Temp capdecmt NO/YES RO
47 Capacity Inh Hi Current capinham NO/YES RO
48 Capacity Dec Hi Current capdecam NO/YES RO
49 Capacity Dec Low Temp capdecls NO/YES RO
50 Capacity Inh DSH capinhsh NO/YES RO
RO Read Only