CL-5
NOTE: Default setting is OCCUPIED 24 hours/day.
23XRV PIC III VFD_CONF TABLE CONFIGURATION SHEET
23XRV PIC III CCN TIME SCHEDULE CONFIGURATION SHEET OCCPC03S
Day Flag
Occupied
Time
Unoccupied
Time
MTWTFSSH
Period 1:
Period 2:
Period 3:
Period 4:
Period 5:
Period 6:
Period 7:
Period 8:
DESCRIPTION RANGE UNITS DEFAULT VALUE
Motor Nameplate Voltage 380 to 480 VOLTS 480
Compressor 100% Speed
54 to 110 (Q,R Compressors)
54 to 140 (P Compressor)
Hz 70
Rated Line Voltage 208 to 600 VOLTS 460
Rated Line Amps 10 to 5000 AMPS 200
Rated Line Kilowatts 0 to 999999 KW 100
Motor Rated Load KW 0 to 999999 KW 100
Motor Rated Load Amps 10 to 5000 AMPS 200
Motor Nameplate Amps 10 to 5000 AMPS 100
Motor Nameplate RPM
1500 to 3500 (Q,R Compressors)
1500 to 3960 (P Compressor)
2672
3750
Motor Nameplate KW 0 to 999999 KW 100
Inverter PWM Frequency
(0=4 k Hz, 1=2 k Hz)
0/1 0
Skip Frequency 1 0.0 to 102 Hz 102
Skip Frequency 2 0.0 to 102 Hz 102
Skip Frequency 3 0.0 to 102 Hz 102
Skip Frequency Band 0.0 to 102 Hz 0
Line Voltage % Imbalance 1 to 10 % 10
Line Volt Imbalance Time 1 to 10 SEC 10
Line Current % Imbalance 5 to 40 % 40
Line Current Imbal Time 1 to 10 SEC 10
Motor Current % Imbalance 5 to 40 % 40
Motor Current Imbal Time 1 to 10 SEC 10
Increase Ramp Time
5 to 60 (Q,R Compressors)
0 to 255 (P Compressor)
SEC 30
Decrease Ramp Time
5 to 60 (Q,R Compressors)
5 to 255 (P Compressor)
SEC 30
Single Cycle Dropout 0/1
DSABLE/
ENABLE
DSABLE