23XRV PIC III SETPOINT TABLE CONFIGURATION SHEET
Upload all Control Configuration tables via Service Tool Yes
No
ICVC Software Part # (See ICVC CONFIGURATION Screen):
ICVC Controller Identification (See ICVC CONFIGURATION Screen): BUS: ADDRESS:
VFD Gateway Version # (See VFD_STAT Screen):
VFD Inverter Version # (See VFD_STAT Screen):
VFD Rectifier Version # (See VFD_STAT Screen):
NOTE: Default setting is OCCUPIED 24 hours/day.
NOTE: Default setting is UNOCCUPIED 24 hours/day.
DESCRIPTION RANGE UNITS DEFAULT VALUE
Base Demand Limit 40 to 100 % 100
LCL Setpoint 10 to 60 (-12.2 to 15.6) ° F (° C) 50.0 (10.0)
ECL Setpoint 15 to 65 (-9.4 to 18.3) ° F (° C) 60.0 (15.6)
Ice Build Setpoint 15 to 60 (-9.4 to 15.6) ° F (° C) 40 (4.4)
Tower Fan High Setpoint 55 to 105 (13 to 41) ° F (° C) 75 (23.9)