CL-3
INITIAL START:
Check Position of all Valves:
Isolation Valves (See Fig. 2-4, 41-43, and 45)
Start Liquid Pumps and Establish Liquid Flow
Oil Level OK and Oil Temperature OK Oil Pressure
Restart Compressor, Bring Up To Speed. Shut Down. Any Abnormal Coastdown Noise? Yes* No
*If yes, determine cause.
START MACHINE AND OPERATE. COMPLETE THE FOLLOWING:
A: Trim charge and record under Charge Refrigerant Into Chiller section on page 79.
B: Inspect refrigerant cooling lines for condensation (Q,R compressors only). See page 71.
B: Complete any remaining control calibration and record under Controls section (pages 18-60).
C: Take at least two sets of operational log readings and record.
D: After machine has been successfully run and set up, shut down and mark shutdown oil levels.
E: Give operating instructions to owner’s operating personnel. Hours Given:
Hours
F: Call your Carrier factory representative to report chiller start-up.
G: Rockwell/Allen Bradley VFD: Register drive start-up at www.automation.rockwell.com/warp.
Eaton VFD: Complete Eaton Warranty Registration Form TD08H28TE and send to:
VFDAftermarketEG@eaton.com
NOTE: To extend drive warranty, registration should be performed by a Rockwell or Eaton Certified Technician as
applicable.
H: Return a copy of this completed checklist to the local Carrier Service office.
SIGNATURES:
CARRIER
TECHNICIAN
DATE
CUSTOMER
REPRESENTATIVE
DATE
VALVE LOCATION OPEN
Discharge Under Muffler ________
Cooler Inlet Next to economizer or under cooler ________
Hot Gas Bypass Between cooler and condenser ________
Vaporizer Condenser Gas Between cooler and condenser ________
Oil Pump Next to oil pump inlet ________
Oil Filter Downstream of oil filter ________
Oil Pressure Regulator Under oil sump next to oil pressure regulator ________
Filter/Drier Next to condenser float chamber ________
Filter/Drier Under condenser near filter/drier ________
VFD Refrigerant Cooling Inlet Under compressor discharge ________
VFD Refrigerant Cooling Drain Between cooler and condenser ________
Relief Valve Three-Way Valves
Cooler (if installed) Fully Front Seated or Fully Back Seated ________
Condenser Fully Front Seated or Fully Back Seated ________
Service Valves
CLOSED
Cooler Refrigerant Charging Valve On cooler relief valve tree ________
Cooler Refrigerant Pumpout Valve Under cooler ________
Condenser Refrigerant Charging Valve On condenser relief valve tree ________
Condenser Refrigerant Pumpout Valve On condenser float valve chamber ________
Oil Sump Charging/Drain Valve Under oil sump ________