CL-7
23XRV PIC III SETUP1 TABLE CONFIGURATION SHEET
DESCRIPTION RANGE UNITS DEFAULT VALUE
Comp Motor Temp Override
150 to 200
(66 to 93)
° F
(° C)
200
(93)
Cond Press Override
145 to 166
(1000 to 1145)
PSI
(kPa)
145
(1000)
Comp Discharge Alert
125 to 160
(52 to 71)
° F
(° C)
140
(60)
Rectifier Temp Override,
Q,R Compressors
155 to 170
(68 to 77)
° F
(° C)
160
(71)
Rectifier Temp Override,
P Compressor
155 to 190
(68 to 88)
° F
(° C)
180
(82)
Inverter Temp Override,
Q,R Compressors
155 to 170
(68 to 77)
° F
(° C)
160
(71)
Inverter Temp Override,
P Compressor
155 to 190
(68 to 88)
° F
(° C)
180
(82)
Chilled Medium 0/1 WATER/BRINE WATER
Chilled Liquid Deadband
0.5 to 2.0
(0.3 to 1.1)
ˆF
(ˆC)
1.0
(0.6)
Evap Refrig Trippoint
10 to 40.0
(–12.2 to 4.4)
° F
(° C)
33
(0.6)
Refrig Override Delta T
Q,R Compressors
2.0 to 5.0
(1.1 to 2.8)
ˆF
(ˆ C)
3
(1.7)
Refrig Override Delta T
P Compressor
2.0 to 10.0
(1.1 to 5.6)
ˆF
(ˆC)
5
(2.8)
Evap Approach Alert
Q,R Compressors
0.5 to 30.0
(0.3 to 16.6)
ˆF
(ˆC)
5
(2.8)
Evap Approach Alert
P Compressor
0.5 to 10.0
(0.3 to 5.6)
ˆF
(ˆC)
4
(2.2)
Cond Approach Alert
0.5 to 30.0
(0.3 to 16.6)
ˆF
(ˆC)
6
(3.3)
Condenser Freeze Point
–20 to 35
(–28.9 to 1.7)
° F
(° C)
34
(1.1)
Flow Delta P Display 0/1 DSABLE/ENABLE DSABLE
Evap Flow Delta P Cutout
0.5 to 50.0
(3.4 to 344.8)
PSI
(kPa)
5.0
(34.5)
Cond Flow Delta P Cutout
0.5 to 50.0
(3.4 to 344.8)
PSI
(kPa)
5.0
(34.5)
Oil Press Verify Time 15 to 300 SEC 45
Liquid Flow Verify Time 0.5 to 5 MIN 5
Recycle Control
Restart Delta T
2.0 to 10.0
(1.1 to 5.6)
ˆF
(ˆ C)
5
(2.8)
Shutdown Delta Speed
(Q, R Compressors)
0.0 to 20.0 % 2.0
Shutdown Delta Speed
(P Compressor)
–10.0 to 20.0 % 0.5
Shutdown Delta T
2.0 to 10.0
(1.1 to 5.6)
ˆF
(ˆ C)
5
(2.8)
SPARE ALERT/ALARM ENABLE
Disable=0, Lo=1/3, Hi=2/4
Spare Temp #1 Enable 0 to 4 0
Spare Temp #1 Limit
–40 to 245
(–40 to 118)
° F
(° C)
245
(118)
Spare Temp #2 Enable 0 to 4 0
Spare Temp #2 Limit
–40 to 245
(–40 to 118)
° F
(° C)
245
(118)
516