CL-8
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
23XRV PIC III SETUP2 TABLE CONFIGURATION SHEET
23XRV PIC III SETUP3 TABLE CONFIGURATION SHEET
23XRV PIC III SETUP4 DISPLAY SCREEN (P COMPRESSOR ONLY)
DESCRIPTION STATUS UNITS DEFAULT VALUE
Capacity Control
Proportional Inc Band
Q,R Compressors
2 to 10
6.5
Proportional Inc Band
P Compressor
2 to 15 12
Proportional Dec Band 2 to 10 6.0
Proportional ECL Gain 1 to 3 2.0
VFD Control
VFD Gain 0.1 to 1.5 0.75
VFD Minimum Speed 15 to 50 % 20
VFD Maximum Speed 50 to 100 % 100
Vaporizer Heater Mode 0 to 1 0
0 = Normal, 1 = Service
Oil Reclaim Min Output 0 to 25 % 25
DESCRIPTION STATUS UNITS DEFAULT VALUE
Oil Sump and Vap. Heater Control
Vap. Heater Turn On Speed 550 to 950 RPM 595
Vap. Heater Turn Off Speed 600 to 2500 RPM 625
Vap. Heater Turn On Lift 18 to 30 (10 to 17) ^F (^C) 22.5 (12.5)
Vap. heater Turn Off Lift 25 to 30 (14 to 19) ^F (^C) 26 (14.4)
Cond. Refrig Temp Low Limit 55 to 80 (33 to 27) °F (°C) 70 (21)
Sump Heater Turn On Speed 550 to 850 RPM 700
Sump Heater Turn Off Speed 600 to 2500 RPM 750
Sump Heater Turn On Lift 18 to 30 (10 to 17) ^F (^C) 22.0 (12)
Sump Heater Turn Off Lift 20 to 60 (11 to 33) ^F (^C) 40 (22)
DESCRIPTION STATUS UNITS DEFAULT VALUE
Economizer Control
Economizer Option 0/1 DS/ENABLE
DSABLE
Econ Activate Speed 20 to 100 %
50
Econ Activate Deadband 0 to 20 %
10
Econ EXV Max Movement 0.5 to 5.0 %
3.0
Superheat Setpoint 0.0 to 20.0 (0.0 to 11.1) ^F (^C)
6.0 (3.3)
Econ Proportional Gain 0.1 to 2.0
0.1
Econ PID Calc Time 10 to 120 SEC
25