Table 3 — ICVC Display Data (cont)
EXAMPLE 15 — VFD_HIST DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
5. Scroll down to highlight .
NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation;
forcing shall not be supported on maintenance screens.
EXAMPLE 16 — LOADSHED DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
5. Scroll down to highlight .
NOTE: All variables with CAPITAL LETTER point names are avail-
able for CCN read operation; forcing shall not be supported on main-
tenance screens.
DESCRIPTION STATUS UNITS POINT
VFD FAULT HISTORY
Values At Last Fault:
Line Current Phase 1 (R) 0 to 99999 AMPS LNAMPS1H
Line Current Phase 2 (S) 0 to 99999 AMPS LNAMPS2H
Line Current Phase 3 (T) 0 to 99999 AMPS LNAMPS3H
Load Current Phase 1 (U) 0 to 99999 AMPS LDAMPS1H
Load Current Phase 2 (V) 0 to 99999 AMPS LDAMPS2H
Load Current Phase 3 (W) 0 to 99999 AMPS LDAMPS3H
Line Voltage Phase 1 (RS) 0 to 99999 VOLTS LNVOLT1H
Line Voltage Phase 2 (ST) 0 to 99999 VOLTS LNVOLT2H
Line Voltage Phase 3 (TR) 0 to 99999 VOLTS LNVOLT3H
Ground Fault Current 0 to 999 AMPS GF_AMPSH
Line Frequency 0 to 99 Hz LINEFRQH
Line Power Factor 0 to 2.0 LINE_PFH
Line Current Imbalance 0 to 100 % LN_IMBIH
Line Voltage Imbalance 0 to 100 % LN_IMBVH
Motor Power Factor 0 to 2.0 MOTORPFH
Motor Current Imbalance 0 to 100 % MT_IMBIH
Motor Overload 0 to 100 % MOTOROVH
Line Active Current 0 to 99999 AMPS AMPSACTH
Line Reactive Current 0 to 99999 AMPS AMPS_REH
Line Active Voltage 0 to 99999 VOLTS VOLTACTH
Line Reactive Voltage 0 to 99999 VOLTS VOLT_REH
DC Bus Voltage 0 to 99999 VOLTS BUSVOLTH
DC Bus Voltage Reference 0 to 99999 VOLTS BUS_REFH
Flux Current 0 to 99999 AMPS FLUXAMPH
Torque Current 0 to 99999 AMPS TORQAMPH
Inverter Temperature 0 to 300 °F (°C) INVTEMPH
Rectifier Temperature 0 to 300 °F (°C) RECTEMPH
VFD Dewpoint 0.0 to 300.0 °F (°C) VFDDEWPT
VFD Enclosure Temp 0 to 300 °F (°C) VFDENCLH
VFD Cold Plate Temp 0 to 300 °F (°C) CP_TEMPH
Actual VFD Speed 0 to 100 % VFD_ACTH
Comp Motor RPM 0 to 300000 rpm CPR_RPMH
Comp Motor Frequency 0 to 10000 Hz VFDFREQH
Chiller Fault State 200 to 272 VFDSTATH
VFD Fault Code 200 to 272 VFD_FLTH
MENU
SERVICE
CONTROL ALGORITHM STATUS
SELECT
VFD_HIST
MENU
SERVICE
CONTROL ALGORITHM STATUS
SELECT
LOADSHED
DESCRIPTION STATUS UNITS POINT
LOADSHED FUNCTION
Redline 0/1 NO/YES REDLINE
Loadshed 0/1 NO/YES LOADSHED
Loadshed Timer 0 to 480 LOADTIME