39
Table 3 — ICVC Display Data (cont)
EXAMPLE 17 — WSMCHLRE DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
5. Scroll down to highlight .
NOTE: All variables with CAPITAL LETTER point names are avail-
able for CCN read operation; forcing shall not be supported on main-
tenance screens.
EXAMPLE 18 — NET_OPT DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
5. Scroll down to highlight .
NOTE: No variables are available for CCN read or write operation.
DESCRIPTION STATUS UNITS POINT
WSM Active? 0/1 NO/YES WSMSTAT
Chilled Water Temp 0.0 to 99.9 °F (°C) CHWTEMP
Equipment Status 0/1 OFF/ON CHWRST
Commanded State TEXT CHWRENA
CHW Setpoint Reset Value 0.0 to 25.0 ^F (^C) CHWRVAL
Current CHW Set Point 0.0 to 99.9 °F (°C) CHWSTPT
DESCRIPTION STATUS UNITS POINT DEFAULT
Loadshed Function
Group Number 1 to 16 ldsgrpn 0
Demand Limit Decrease 0 to 60 % ldsdlta 20
Maximum Loadshed Time 30 to 480 MIN maxshed 120
CCN Occupancy Config:
Schedule Number 3 to 99 occ_num 3
Broadcast Option 0 to 1 DSABLE/ENABLE occbrcst DSABLE
Alarm Configuration
Re-Alarm Time 0 to 1440 MIN retime 30
Alarm Routing 0 to 1 routing 10000000