Table 3 — ICVC Display Data (cont)
EXAMPLE 19 — VFD_CONF DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
5. Scroll down to highlight .
NOTE: Those parameters marked with a * shall not be downloaded to the VFD, but shall be used in other calculations and algorithms in the ICVC.
DESCRIPTION STATUS UNITS POINT DEFAULT
Motor Nameplate Voltage 380 to 480 VOLTS
motor_nv
480
Compressor 100% Speed
54 to 110
(Q,R Compressors)
54 to 140
(P Compressor)
Hz
comp_100
70
* Rated Line Voltage
208 to 600 VOLTS
vfd_volt
460
* Rated Line Amps
10 to 5000 AMPS
vfd_amps
200
* Rated Line Kilowatts
0 to 999999 KW
vfd_rlkw
100
*Motor Rated Load KW
0 to 999999 KW
mot_rlkw
100
*Motor Rated Load Amps
10 to 5000 AMPS
mot_rla
200
Motor Nameplate Amps
10 to 5000 AMPS
motorni
100
Motor Nameplate RPM
1500 to 3960
(Q,R Compressors)
1500 to 3960
(P Compressor)
motorpm
2672
3750
Motor Nameplate kW
0 to 999999 KW
motorkw
100
Inverter PWM Frequency
(0=4 kHz, 1=2 kHz)
0/1
pwm_freq
0
Skip Frequency 1
0 to 102 Hz
skipfrq1
102
Skip Frequency 2
0 to 102 Hz
skipfrq2
102
Skip Frequency 3
0 to 102 Hz
skipfrq3
102
Skip Frequency Band
0 to 102 Hz
skipband
0
Line Voltage % Imbalance
1 to 10 %
v_umbal
10
Line Voltage Imbal Time
1 to 10 SEC
v_time
10
Line Current % Imbalance
5 to 40 %
lineim_i
40
Line Current Imbal Time
1 to 10 SEC
lineim_t
10
Motor Current % Imbalance
5 to 40 %
motim_i
40
Motor Current Imbal Time
1 to 10 SEC
motim_t
10
Increase Ramp Time
5 to 60
(Q,R Compressors)
0 to 255
(P Compressor)
SEC
ramp_inc
30
Decrease Ramp Time
0 to 60
(Q,R Compressors)
5 to 255
(P Compressor)
SEC
ramp_dec
255
30
Single Cycle Dropout
0/1
DSABLE/ENABLE cycdrop
DSABLE
516