Table 3 — ICVC Display Data (cont)
EXAMPLE 20 — OPTIONS DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
5. Scroll down to highlight .
NOTE: No variables are available for CCN read or write operation.
MENU
SERVICE
EQUIPMENT SERVICE
SELECT
OPTIONS
DESCRIPTION STATUS UNITS POINT DEFAULT
Auto Restart Option 0/1 DSABLE/ENABLE
astart
DSABLE
Remote Contacts Option 0/1 DSABLE/ENABLE
r_contac
DSABLE
Soft Stop Amps Threshold 40 to 100 %
softstop
100
Hot Gas Bypass
HGBP Option 0, 1, 2 0=DSABLE
1=HGBP
2=LOW LOAD HGBP
Srg_hgbp
DSABLE
Min. Load Point (T1,P1)
HGBP Delta T1 0.5 to 20 (0.3 to 11.1) ^F (^C)
hgbp_dt1
1.5 (0.8)
HGBP Delta P1 10 to 170 (68.9 to 1172.2) psi (kPa)
hgbp_dp1
150 (1034.2)
Full Load Point (T2,P2)
HGBP Delta T2 0.5 to 20 (0.3 to 11.1) ^F (^C)
hbgp_dt2
4 (2.2)
HGBP Delta P2 30 to 250 (206.9 to 1724) psi (kPa)
hgbp_dp2
200 (1379)
HGBP Deadband 0.5 to 3 (0.3 to 1.7) ^F (^C)
hbgp_db
1 (0.6)
HGBP On Delta Speed 0.0 to 20.0 %
hgbp_on
5.0
HGBP Off Delta Speed 0.0 to 20.0 %
hgbp_off
3.0
Stall Protection
Stall Delta % Amps 5 to 20 %
stall_a
10
Stall Time Period 7 to 10 MIN
stall_t
8
Ice Build Control
Ice Build Option 0/1 DSABLE/ENABLE
ibopt
DSABLE
Ice Build Termination 0 to 2
ibterm
0
(0=TEMP, 1=Contact, 2=Both)
Ice Build Recycle 0/1 DSABLE/ENABLE
ibrecyc
DSABLE
Refrigerant Leak Option 0/1 DSABLE/ENABLE
leak_en
DSABLE
PPM at 20mA 0 to 99999
ppm_20
1000
Refrig Leak Alarm PPM 0 to 99999
ppm_lim
500
Head Pressure Reference
Delta P at 0% (4mA) 20 to 85 (138 to 586) psi (kPa)
hpdp0
25 (172)
Delta P at 100% (20mA) 20 to 85 (138 to 586) psi (kPa)
hpdp100
50 (345)
Minimum Output 0 to 100 %
hpdpmin%
0