12.2.6 - Unit operation with a free cooling drycooler
12.2.6.1 - Operating principle
The units have been designed to optimise the operation of the 
systems, using drycoolers as a free cooling system (method using 
low outdoor air temperatures to chill the water in the air conditioning 
system).
This system enables substantial energy and cost savings, and is 
at its most eective when the outdoor air temperature is low.
The unit's SmartVu
TM
 control system includes algorithms which 
enables the following to be constantly automatically optimised: 
 - the operation of the drycooler fans,
 - the variation of the ow rate in the water loop, 
 - the cooling capacity (the drycooler and chiller can operate 
independently or simultaneously),
 - the positions of the valves, depending on the operating mode.
The  control  denes  the  optimal  conguration,  taking  the  water 
setpoint value, outdoor air temperature, and water loop 
temperature into account (the control will give priority to the 
drycooler).
Parallel control of the fans and of the variable ow rate in the water 
loop enable the system to operate at outdoor temperatures of 
down to -20 °C without any additional control.
Warning: the drycooler and chiller both need to be equipped 
with the Free cooling management option.
Chiller
LEN communication bus
3
2
1
Drycooler free cooling
2-way valve control
No
NC
OAT
For an optimal free cooling operation, the chiller has to be 
congurated:
 - using the water inlet temperature control,
 - using the temperature delta control for the variable-speed 
pump option.
12.2.6.2 - Communication to control the drycooler
When the option is selected, a specific electronic board is 
integrated in the control box of the drycooler. A communication 
LEN bus connected between the drycooler (board AUX1) and the 
chiller  is needed  for the overall system control.
This cable must be a 3-point Wago type cable (5 mm spacing or 
equivalent) and must be shielded.
The board integrated in the drycooler electrics box has analogue 
inputs for the outside air temperature (mark 1), water loop return 
temperature sensor (mark 3) and drycooler leaving water 
temperature sensor (mark 2), as well as digital outputs permitting 
the control of the fans. 
The option works as if the system was split in two parts: 
The chiller (with free cooling option)
• Dedicated control algorithms with LEN connector to 
communicate and control the drycooler. 
The drycooler (with free cooling option):
• AUX board with the I/O,
• room air temperature sensor to be placed outdoors,
• drycooler water outlet temperature sensor (factory-tted), 
• water loop temperature sensor (to be tted on the common 
pipe upstream of the valve), 
• Control & 230V power supply  for 2 two ways valve or one 
three ways valve
The dierence between the drycooler outdoor air temperature and 
the water loop sensor temperature determines whether or not it 
is possible to activate free cooling mode.
12.2.6.3 - Conguration of the fan control 
To set the conguration corresponding to the drycooler installed 
(number of fans, control type – xed or variable speed), please 
refer to the instructions in the SmartVu
TM
 control manual. Using 
these parameters, the SmartVu
TM
 control will activate the correct 
number of outputs to control the fans.
SmartVu
TM
 controls the automatic switching of all fans, based on 
operating time and number of start-ups, to ensure the fan motors 
provide a long service life.
Compatible fans conguration:
 - 1 to 20 fans,
 - xed speed or variable speed,
 - 1 or 2 rows of fans.
Refer to the drycooler wiring diagram to see the arrangement of 
the fan stages.
12.2.6.4 - Valves on the water loop
The free cooling system requires 2 two-way valves (one normally 
open, one normally closed) or a three-way valve, not supplied with 
the unit or the drycooler. 
A two-way valve kit is available in the list of accessories for the 
drycooler.
The drycooler electrics box has a 230 V power supply for 2 two-
way valves.
Recommended motor valve (per default): 230V 3 points
See the drycooler wiring diagram for cabling the valves to the 
customer terminal strip.
12.2.6.5 - Guidelines for system installation
For physical characteristics, dimensions, performances: refer to 
the drycooler documentation.
For the electrical connections, see the electrical wiring diagram 
supplied with the drycooler.
For software configuration information, refer to the control 
documentation of the chiller.
For a proper drycooler installation, follow the professional 
guidelines for the following topics:
 - sizing of the water piping;
 - pressure drops (verify that the operating pressure of the unit 
pump is sucient compared to the pipe and valve pressure 
drops; check for all operating modes);  
 - maximum height for the drycooler (in relation to the unit safety 
valve); 
 - Good positioning for temperature sensors: outside air 
temperature and water loop temperature .
12 - OPTIONS 
44