Type B Electronic Control
GB - 2
     
     
Fig. 5
  ON/OFF/fan speed selector
  Blue LED - cooling operation
  Seasonal changeover button
  Red LED - heating operation
  Energy saving button
  Yellow LED - energy saving operation
 Temperature knob
 Automatic seasonal changeover
Type “B” control is used in 4-pipe systems and 2-pipe systems with 
electric heater. 
Functions
Control "B" have a knob to select the temperature, with a range 
from 10°C to 30°C, and room temperature is maintained at the 
selected value.
Fan operation
With the fan speed selector  fan mode can be set either manually 
or automatically. 
In the manual mode it is possible to select three fan speeds (low/ 
medium/high) according to personal preference. 
In the auto mode fan speed is regulated by a microprocessor in the 
control in relation to the temperature chosen. 
During installation, it is possible to select continuous fan operation 
via the switch located on the electronic board (see paragraph “Dip-
switch confi guration”).
In the heating mode, the fan operation is delayed by approximately 
one minute to allow the residual heat on the heat exchanger coil or 
the electric heater (if any) to be released.
20°c
O
FF
AUTO
A
Wall-mounted control
•  Remove the control cover, unscrewing the screw located in the 
bottom part (Fig. 2). Secure the control to the wall, marking the 
drill holes.
•  Drill the holes previously marked. 
  Avoid drilling with the control already placed on wall.
•  Prepare electrical connections between the control terminal block and 
the unit control box panel as shown in the wiring diagram in fi g. 9.
  For the specifi c connection between the control and the fan coil 
unit refer to the diagram shown on the unit.
•  Remove the cable protection guard  and carry out the connec-
tions to the control terminal block (Fig. 3).
  The connecting cable of the fan coil unit and the accessory cables 
should be of the H07 RN-F type (or higher) according to EN 
60335-2-40 standard.
  All electric connection cables should be at least 1,5 mm.
  The maximum connecting distance between unit and control 
should not exceed 15 metres.
•  After connections to the terminal block have been made, replace 
the cable protection guard as shown in the fi gure (Fig. 4).
•  Fix the control to the wall using the corresponding screw anchors .
•  Put the control cover back to its place by reinstalling the screw 
previously removed
 
(Fig. 2).
IMPORTANT:
• All connections between the unit and the control must be 
placed into a proper plastic conduit.
• Handle the control with extreme care. Do not touch electronic 
components to avoid damaging them.
Fig. 2
 Screw
 Screw anchor
  Screw to close the control
Assembly
CONTROL  TYPE "B"
Control
Fig. 3 Fig. 4