GB - 3
Type B Electronic Control
ENGLISH
Frost - protection
This function keeps the temperature from dropping below 7°C in 
rooms not used for long periods of time. 
When this temperature is reached, the control activates the valve 
and puts the fan on high speed. 
The frost protection function can be activated through the associ-
ated micro-switch (see dip switch confi guration); if enabled, this 
function activates even when the control is in the OFF position.
Energy saving
This function is especially useful when air conditioning at night or 
in rooms where the user is likely to be absent for a longer period of 
time.
In this case, pushing button 
 raises the temperature during cooling  
by 4°C and lowers it during heating by 4°C.
Enabling this function (yellow LED ON) cuts out other displays.
During energy saving, even the brightness of the yellow LED is 
dimmed.
Seasonal changeover
Manual
Selection of heating/cooling is done manually by pushing the button 
on the control.
Automatic
The automatic seasonal changeover allows automatic switching of 
the fan coil operating mode to cooling or heating, depending on the 
temperature set by the user and on the room temperature.
External contact
The control has an input that can be used as window contact or 
presence detection.
When such a signal is activated (presence of line voltage on the 
terminal block contact) the control is set to OFF mode. 
As a consequence, all outputs (fan, valves etc.) are disconnected, 
and only the frost protection is active, if switched ON by the ap-
propriate dip-switch.
Additional heating 
This function allows the water soilenoid valve and the electric hea-
ters to work simultaneously.
With this function activated by the dip switch (no. 5) – see section 
microswitch confi guration (dip switch) – the function is active.
To avoid overheating due to simultaneous operation of water and 
heating elements, the temperature of  the incoming water of the coil 
is adjusted by a special sensor (optional) that must be positioned 
on the inlet pipe.
If the function is active but the sensor is not connected,  the control 
enters the alarm mode, the red led fl ashes and all the user devices 
are switched off.
Sensor installation:
Open the control by loosening the screw  used to close the con-
trol (see fi g. 6). 
Connect the sensor on the connector side of the electronic board to 
connector 
 (see fi g. 6). 
Connect the other end to the inlet water pipe using the clip and the 
strips supplied (see fi g. 7) .
Complete by insulating the pipe with the insulating tape supplied.
Control
Use: 
ON/OFF/fan speed selector
OFF  In this position the control is OFF and all functions are disa-
bled.
  If the frost protection function is selected by the dip-switch, 
this is activated even if the control is in OFF position.
  With selector in this position, the fan operates at low speed.
  With selector in this position, the fan operates at medium 
speed.
  With selector in this position, the fan operates at high 
speed.
AUTO  The control maintains the selected temperature, acting 
automatically on the fan speed.
Temperature selector 
Its purpose is to maintain the temperature at the desired level.The 
reference value at the centre of the range is 20°C .
By turning the knob towards the symbol ( – ) the temperature is 
reduced from the original setting (minimum value is 10°C).
By turning the knob towards the symbol ( + ), the temperature is 
raised from the original setting (maximum value is 30°C).
Fig. 7
  Screw to close the control
  Water temperature sensor
Fig. 6
X1 : Water probe (optional)
X2 : Air probe
X3 : Jumper for enabling 
the probe on air inlet