START-UP
Differential Enthalpy Switchover Strategy —
On cer-
tain EconoMi$er controller models, the differential enthalpy
switchover strategy must be enabled manually.
To determine the controller model, refer to the label on the
front of the controller. Models AD-DME1701-0 require no
commissioning for differential enthalpy switchover strategy.
Models AD-DME1701-1 or AD-DME1711-1 require manual
configuration.
To enable differential enthalpy: Press and hold the CONFIG
button for more than 30 seconds, then release. The light-
emitting diode (LED) flashes twice and the controller resumes
normal operation. To return to single enthalpy mode, press and
hold the CONFIG button for more than 30 seconds, then re-
lease. The LED flashes once and the controller resumes normal
operation.
Operating Sequence
COOLING — When the Outdoor Air Temperature (OAT) is
above the ECON SP set point and the room thermostat calls for
Stage 1 cooling (R to G + Y1), the indoor-fan motor (IFM) is
energized and the EconoMi$er damper modulates to minimum
position. The compressor contactor is energized starting the
compressor and outdoor-fan motor (OFM). After the thermo-
stat is satisfied, the damper modulates to the fully closed posi-
tion when the IFM is deenergized.
When the OAT is below the ECON SP setting and the room
thermostat calls for Stage 1 cooling (R to G + Y1), the
EconoMi$er modulates to the minimum position when the
IFM is energized. The EconoMi$er provides Stage 1 of cooling
by modulating the return and outdoor air dampers to maintain a
55 F supply air set point. If the supply-air temperature (SAT) is
greater than 57 F, the EconoMi$er modulates open, allowing a
greater amount of outdoor air to enter the unit. If the SAT drops
below 53 F, the outdoor-air damper modulates closed to reduce
the amount of outdoor air. When the SAT is between 53 and
57 F, the EconoMi$er maintains its position.
If outdoor air alone cannot satisfy the cooling requirements
of the conditioned space, and the OAT is above the MECH
CLG LOCKOUT set point, the EconoMi$er integrates free
cooling with mechanical cooling. This is accomplished by the
strategies below.
NOTE: Compressors have a two-minute Minimum On, Mini-
mum Off, and Interstage delay timer.
1. If Y1 is energized, and the room thermostat calls for
Y2 (2-stage thermostat), the compressor number 1 and
OFM are energized. The position of the EconoMi$er
damper is maintained at its current value.
2. If Y1 is energized for more then 20 minutes, and Y2 is
not energized (whether or not a 2-stage thermostat is
used), compressor no. 1 and OFM are energized. The
position of the EconoMi$er damper is maintained at its
current value.
0
200
400
600 800 1000
1200
1400 1600
FLOW (CUBIC FEET/MINUTE)
0.5
0.4
0.3
0.2
0.1
0
STATIC PRESSURE (IN. WG)
0
400
800
1200
1600
2000
2400
FLOW (CUBIC FEET/MINUTE)
0.5
0.4
0.3
0.2
0.1
0
STATIC PRESSURE (IN.WG)
STATIC PRESSURE (in. wg)
0.25
0.20
0.15
0.10
0.05
0.00
0
200
400
600
FLOW IN CUBIC FEET PER MINUTE (cfm)
800 1000
Fig. 41 — 3 to 6 Ton Barometric Relief Capacity
(Vertical EconoMi$er)
Fig. 42 — 7
1
/
2
to 12
1
/
2
Ton Barometric Relief
Capacity (Vertical EconoMi$er)
Fig. 43 — Barometric Flow Capacity
3 to 6 Ton
7
1
/
2
to 12
1
/
2
To n
Fig. 44 — Outdoor Air Leakage
3 to 6 Ton
7
1
/
2
to 12
1
/
2
To n
FLOW IN CUBIC FEET PER MINUTE (cfm)
STATIC PRESSURE (in. wg)
0.00
0.10
0.20
0.30
0.40
0.50
80
60
40
20
0
FLOW IN CUBIC FEET PER MINUTE (cfm)
0
1000 2000 3000 4000
5000
0.40
0.35
0.30
0.25
0.20
0.15
0.10
0.05
0.00
STATIC PRESSURE (in. wg)
Fig. 45 — Return Air Pressure Drop
3 to 6 Ton
7
1
/
2
to 12
1
/
2
To n

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier CRECOMZR 004A01 Series and is the answer not in the manual?

Carrier CRECOMZR 004A01 Series Specifications

General IconGeneral
BrandCarrier
ModelCRECOMZR 004A01 Series
CategoryAir Conditioner Accessories
LanguageEnglish

Related product manuals