15
Remote (Downstairs) Monitoring of Control-
ler’s Fault Detection and Diagnostics
Many codes including IECC, Title 24, and ASHRAE 90.1
require that the economizers faults be accessible by operat-
ing or service personal, or annunciated locally on zone ther-
mostat. To setup remote monitoring on the controller, under
SYSTEM SETUP, AUX1-OUT must be set to SYS.
The latest versions of Honeywell’s TH8321WF or
TH8321R thermostats are options for meeting this require-
ment. Figure 33 shows an example of the thermostat wiring to
the Jade controller. Follow instructions provided with Honey-
well thermostat.
Another option that is acceptable to some codes is an an-
nunciator light visible by service personnel. See Fig. 34 for
typical wiring to the Jade controller. Refer to codes for proper
labeling of light.
Fig. 33 — Thermostat Wired For Remote FDD
Fig. 34 — Annunciator Light Wired for Remote FDD
CR
AUX2-1
OCC
E-GND
EXH1
AUX1-0
Y2-I
Y2-O
Y1-I
Y1-O
C
R
W7220 JADE
ECONOMIZER
U1
U1
R
Rc
C
A-L/A
FURNACE, AIR HANDLER,
OR RTU
TH8321R OR
TH8321WF
SUB-BASE
MAT
JADE Setting: Under the “System Setup” menu, set AUX1-OUT to
“SYS” which will close JADE relay on fault detection
Examples of annunciator lights
would include these Grainger lights:
- Item #20C841
- Item #20C846
AUC2-1
OCC
E-GND
EXH1
AUX1-0
Y21
Y2O
Y1I
Y1O
=CR
IAQ COM
IAQ (2-10V)
IAQ 24V
ACT (2-10V)
ACT COM
ACT 24V
MAT
OAT
OAT
TO “C” TERMINAL
TO “AUX1-0” TERMINAL
Annunciator Light*
W7220 Economizer Controller Module