38
DIAGNOSIS AND SOLUTION (CONT.)
Indoor units mode conflict (match with multi outdoor unit)
NOTE:
No: No mode conflict
Ye s: Mode conflict
Error Code --
Malfunction decision conditions The indoor units cannot work cooling mode and heating at same time. Heating mode has a priority.
Supposed causes
Indoor unit A is operating in the
COOLING
or
FAN
mode, and the indoor unit (B) is set to the
HEATING
mode, therefore unit A powers off and unit B begins operating in the
HEATING
mode.
Indoor unit A is operating in the
HEATING
mode, and indoor unit B is set to the
COOLING
or
FAN
mode,
then unit B changes to the
STANDBY
mode and unit A will not change.
Cooling Mode Heating Mode Fan Off
Cooling Mode No Yes No No
Heating Mode Yes No Yes No
Fan No Yes No No
OFFNoNoNoNo