EasyManua.ls Logo

Carrier DHMVHAQ24XA3 - Wiring; Power and Communication Wiring

Carrier DHMVHAQ24XA3
54 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
:
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
4
ELECTRICAL DATA
Table 3 — Electrical Data
LEGEND
FLA - Full Load Amps
WIRING
All wires must be sized per NEC (National Electrical Code) or CEC
(Canadian Electrical Code) and local codes. Use the Electrical Data table
MCA (minimum circuit amps) and MOCP (maximum over current
protection) to correctly size the wires and the disconnect fuse or breakers
respectively.
Power and Communication Wiring: The main power is supplied to the
outdoor unit. The field supplied 14/3 power/communication wiring,
from the outdoor unit to the indoor unit, consists of four (4) wires and
provides the power for the indoor unit. Two wires are high voltage AC
power, one is communication wiring and the other is a ground wire.
To minimize communication interference: If installed in a high
Electromagnetic field (EMF) area and communication issues arise, a 14/
2 stranded shielded wire can be used to replace 2 (L2/N) and 3 (S)
between the outdoor and indoor units - landing the shield onto the
ground in the outdoor unit only.
Table 4 — Wiring Sizes
HIGH WALL UNIT SIZE
INDOOR FAN
MAX FUSE CB AMP
V-PH-HZ FLA HP
HEAT PUMP MODELS
9K
115-1-60
0.4 0.02
Refer to outdoor unit installation instructions –
Indoor unit powered by the outdoor unit
12K
0.4 0.02
9K
208/230-1-60
0.4 0.027
12K
0.4 0.027
18K
0.4 0.037
24K
0.45 0.06
CABLE CABLE SIZE REMARKS
Connectio
n Cable
14AWG
3 wire + Ground 1Φ 208/230V
(Stranded wire is recommended)
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage
or improper operation.
Wires should be sized based on NEC and local codes.
CAUTION

Related product manuals