5
Table 2 – Menu Structure
a
Menu Parameter
Parameter
Default
Value
Parameter
Range and Increment
b
EXPANDED PARAMETER NAME
Notes
STA TUS
ECON AVAIL NO YES/NO ECONOMIZING AV AIALBLE
YES = economizing available; the system can use outside air for free
coo ling when required
ECONOMIZING NO YES/NO ECONOMIZING ACTIVE
YES = Outside air being used for 1
st
stag e cooling.
NO = Econom izing not act ive
OCCUPIED NO YES/NO OCCUPIED
YES = OCC si gnal received from space thermostat
or unitary cont ro ller.
YES = 24 Vac on termi nal OCC.
NO = 0 Vac on termi nal OCC.
HEAT PUMP n/a
c
COOL
HEAT
HEAT PUMP MODE
(Not available on 2---Speed configurati on)
COOL Y1 ---IN OFF ON/OFF FIRST STAGE COOLING DEMAND (Y1 - --IN)
Y1---I sig na l from sp a c e thermo sta t or unitary cont ro ller for Cooling Stage 1.
ON = 24 Vac on terminal Y1---I
OFF = 0Vac on terminal Y1---I
COOL Y1 ---OUT OFF ON/OFF FIRST STAGE COOLING RELA Y OUTPUT
ON = 24 Vac on terminal Y1---O; Stage 1 mechanical cooling called on
OFF = 0 Vac on terminal Y1---O; no mechanical cooling
COOL Y2 ---IN OFF ON/OFF SECO ND STAVE COO LI NG DEMAND (Y2---IN)
Y2---I sig na l from sp a c e thermo sta t or unitary cont ro ller for Cooling Stage 2.
ON = 24 Vac on terminal Y2---I
OFF = 0 Vac on termi nal Y2---I
COOL Y2 ---OUT OFF ON/OFF SECOND STAGE COOLING RELA Y OUTPUT
ON = 24 Vac on terminal Y2---O; Stage 2 mechanical cooling called on
OFF = 0 Vac on terminal Y2---O; no Stage 2 mechanical cooling
MA TEMP nn_F(or_C) 0 to 140_F
(---18 to 60_C)
SUPPLY AI R TEMPERA TR UE, Cooling Mode
Disp lays value of measured mixed/cooled air from SA T sensor in fan
section.
D isp l a y s --- --- . --- if n o t co n n e ct e d, sh ort o r o u t --- of --- range . S ee Me n u N o te 2
DA TEMP nn_F(or_C) 0 to 140_F
(---18 to 60_C)
DISCHARGE AIR TEMPERATRUE, after Heating section
(Accessory sensor required)
Displays when Discharge Air sensor is connected and displays measured
di s c harg e temp e rature.
D isp l a y s --- --- --- --- --- --- if se n s or se n ds in v a l id v a l u e , if n o t co n n e c te d, sh o r t
or out---of ---range.
OA TEMP nn_F(or_C) ---40 to 140_F
(---40 to 60_C)
OUTSIDE AIR TEMPERATRUE
Disp lays measure d value of outd o or air temp e rat ure.
D isp l a y s --- --- --- --- --- --- if se n s or se n ds in v a l id v a l u e , if n o t co n n e c te d, sh o r t
or out---of ---range.
OA HUM nn% 0 to 100% O UTSIDE AIR RELATIVE HUMIDITY
Displays meas ure d value of outdo or humi d ity from OA enthalpy sens o r.
RA TEMP nn_F(or_C) 0 to 140_F
(---18 to 60_C)
RETURN AIR TEMPERATRUE
(Accessory sensor required)
Disp lay s measured value of return air tempe rat ure from RAT sens o r.
RA HUM nn% 0 to 100% RETURN AIR RELATIVE HUMIDITY
(Accessory enthalpy sensor required)
Disp lay s measure d value of return air humidi t y from RA se ns o r.
IN CO2 ___ppm 0 to 2000 ppm SP ACE/RETURN AIR CO2
(CO
2
sensor required, access ory or factory option)
Disp lays value of measured CO
2
from CO
2
sensor .
Invalid if not connected, short or out---of---range
DCV STATUS n/a ON/OFF DEMAND CONTROL VENTILATI ON STA TUS
(CO
2
sensor required, access ory or factory option)
Disp lays ON if IN CO2 value above setpo int DCV SET and OFF if below
setpoint DCV SET .
DAMPER OUT 2.0V 2.0 to 10.0V Displays voltage output to the damper actuator.
0% = OSA Damper fully closed
100% = OSA Damper full open
SeeMenuNote3.
ACT POS nn% 0 to 100% Displays actual posi t i on of outdoor air damper actuator
2.0V = OSA Damper fully ---closed
10.0V = OSA Damper full open
ACT COUNT n/a 1 to 65535 Displays numbe r of ti m e s actuator has cyc led.
1 Cycle equals acc rue d 180_ of actuator movement in any direc ti on
ACTUATOR n/a OK/Alarm
(on Alarm menu)
Displays Error if voltage or torque is below actuator range
EXH1 OUT OFF ON/OFF EXH AUST STA G E 1 RELAY OUTPUT
Output of EXH1 terminal:
ON = relay closed
OFF = relay open
LLECON--02SI