Table 2 -- Menu Structure
a
(cont)
Menu Parameter
Parameter
Default
Value
Parameter
Range and Increment
b
EXPANDED PARAMETER NAME
Notes
STA TUS
(cont )
EXH2 OUT OFF ON/OFF EXH AUST STA G E 2 RELAY OUTPUT
Out p ut of A UX terminal; disp lays only if A UX = EXH2
ON = relay closed
OFF = relay open
ERV OFF ON/OFF ENERGY RECOVERY UNIT RELA Y OUTPUT
Out p ut of A UX terminal; disp lays only if A UX = ERV
ON = relay closed
OFF = relay open
MECH COOL ON 0 0, 1, or 2 Displays st a g e of mechanical co oling that is act i v e .
FAN SPEED n/a LOW or HIGH SUPPLY FAN SPEED
Displays speed setting of fan on a 2 - --speed fan unit.
W(HEATON) n/a ON/OFF HEAT DEMAND STATUS
Displays st a t us of heat dem and on a 2---spe e d fan unit.
SETPOINTS
MAT SET 53_F
(12_C)
38 to 65_F;
(3 to 18_C)
increment by 1
SUPPLY AIR SETPOI N T
Setpoi nt determines where the economizer will modulate the OA damper to
maintain the mixed air temperature.
SeeMenuNote2.
LOW T LOCK 32_F
(0_C)
---45 to 80_F;
(---43 to 27_C)
increment by 1
COMPRESSOR LOW TEMPERATURE LOCKOUT
Setpoi nt determines outdoor temperature when the mechanical cooling
canno t be turned on.
DRYBLB SET 63_F
(17_C)
48 to 80_F
(9 to 27_C)
increment by 1
OA DRY BULB TEMPERATURE CHANGEOVER SETPOINT
Setpoi nt determines where the economizer will assume outdoor air
temperature is good for free cooling; e.g.: at 63_F(17_C), unit will
economize at 62_F (16.7_C ) and below and not economize a t 64_F
(17.8_C) and above. There is a 2_F(1.1_C)deadband.
SeeMenuNote3
ENTH CURVE ES3 ES1, ES2, ES3, ES4, or
ES5
ENTHALPY CHANGEOVER CURVE
(Re q uires enthalpy se ns o r opt ion)
Enthalp y boundary “curv e s for economizing using single entha lp y.
DCV SET 1100ppm 500 to 2000 ppm;
increment by 100
DEMA N D CONTR OL VENTILATIO N SETPOINT
Disp lays only if CO
2
se nsor is connec t e d . Set p o int for Demand Control
Ventilation of space. Above the setpoint, the OA dampers will modulate
open to bring in additional OA to maintain a space ppm level below the
setpoint.
MIN POS L 6.0 V 2to10Vdc VENTILATION MINIMUM POSITION AT LOW SPEED
Displays ONLY if a CO
2
se nsor is NOT connect ed.
MIN POS H 4.4 V 2to10Vdc VENTILATION MINIMUM POSITION AT HIGH SPEED
Displays ONLY if a CO
2
se nsor is NOT connect ed.
VENTMAX L 6.0 V 2to10Vdc DCV MAXIMUM DAMP ER POSITION AT LOW SPEED
(Requi res CO
2
se nsor conne c ted)
VENTMAX H 4.4 V 2to10Vdc DCV MAXIMUM DAMP ER POSITION AT HIGH SPEED
(Requi res CO
2
se nsor conne c ted)
VENTMIN L 3.7 V 2to10Vdc DCV MIN IMUM DAMP ER POSITION AT LOW SPEED
(Requi res CO
2
se nsor conne c ted)
VENTMIN H 2.8 V 2to10Vdc DCV MI N IMUM DAMP ER POSITION AT HIGH SPEED
(Requi res CO
2
se nsor conne c ted)
ERV OAT SP 32_F
(0_C)
0to50_F;
(---18 TO 10_C)
increment by 1
ENERGY RECOVERY VENTILATION UNIT OUTDOOR AIR TEMPERA TURE
SETPOI NT
Only when AUX1 O = ERV
EXH1 L SET 65% 0 to 100%;
Increment by 1
EXHAUST FAN STA GE 1 SETPO INT AT LO W SPEED
Set p o int for OA dam p e r posi t ion when exhaust fan1 is powere d by the
economizer
EXH1 H SET 50% 0 to 100%;
Increment by 1
EXHA UST FA N STA GE 1 SETPOIN T AT HIGH SPEED
Set p o int for OA dam p e r posi t ion when exhaust fan1 is powere d by the
economizer
EXH2 L SET 80% 0 to 100%;
Increment by 1
EXHAUST FAN STA GE 2 SETPO INT AT LO W SPEED
Set p o int for OA dam p e r posi t ion when exhaust fan1 is powere d by the
economizer. Only used when AUX1---O is set to EHX2.
EXH2 H SET 75% 0 to 100%;
Increment by 1
EXHA UST FA N STA GE 2 SETPOIN T AT HIGH SPEED
Set p o int for OA dam p e r posi t ion when exhaust fan1 is powere d by the
economizer. Only used when AUX1---O is set to EHX2.