EVD4X, ESD4X, WMVC, WMSC: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
2
IMPORTANT: Nitrogen can leak out through the  hole that the needle
pierced in the  plugs. This does  not  indicate a  leaking  coil nor warrant
return of the coil.
IMPORTANT:  Dry  fit  all  connections  to  systems  (electrical,  drains,
refrigerant  lines,  flue  &  intake,  etc.)  first  to  verify  no  interferences
before final connections are made.
Introduction
Use  this  instruction  manual  to  install  indoor  coils  on  upflow  or
downflow furnaces in cooling applications only. Do not use these coils
in  heat  pump  applications.  Do  not  install  in  the  horizontal  position.
These  coils  are  enclosed  in  a  painted  casing,  have  factory-installed
TXVs, and are used with Puron refrigerant R-410A systems. 
Installation
These  units  can  be  installed  in  upflow  or  downflow  configurations.
Before installation, there are several performance requirements that must
be  considered  because  poor  installation  can  negatively  alter
performance. This section will briefly discuss those factors.
Airflow
Airflow  amount  and  distribution  are  vital  to  adequate  system
performance.  Problems  that  can  be experienced  with  incorrect  airflow
include:
• low system performance
• restricted TXV
• frosted coil
• poor humidity control
• water blow-off
When attaching the coil and building the plenum, pay special attention to
the effect these details will have on airflow. After system start-up, check
the cfm to insure that it is correct. (Generally, the cfm should be 350 to
450 cfm/ton during normal cooling operation.)
TXV
A  thermal  expansion  valve  is  utilized  in  this  coil  design  to  optimize
performance  and  comfort throughout  the  entire  operating  range  of  the
system. Special attention needs to be taken to the TXV when installing
the coil (Fig. 1):
• Do not overheat valve. Temperatures that exceed 212°F (100°C) can
harm valve performance. Use a wet cloth or heat sink when brazing.
• Place liquid filter dryer near indoor unit to reduce the risk of debris
clogging the valve.
• Make  sure  TXV  bulb  is  securely  fastened  with  a  metal  strap  and
wrapped in the indentation on vapor line tube.
These specific coils have a factory-installed hard-shutoff TXV designed
only  for  use  with  R-410A  refrigerant.  Use  only  with  outdoor  units
designed for R-410A.
NOTE:  These  TXVs  are  factory  set  at  approximately  10°  superheat
measured at the suction service valve, and are not field adjustable.
A210138
Fig. 1 – TXV Bulb
Cabinet Sweating
If this unit is installed in a garage, attic, or other unconditioned space,
special attention needs to be given to the potential of cabinet sweating. A
6-in (152 mm) wide piece of insulation should be wrapped around the
coil casing and supply duct connection point.
Inspect Equipment
File claim with shipper if equipment is damaged.
Select Installation Procedure
NOTE:  Furnace  coils  are  not  approved  to  be  used  in  fan  coil  or
“draw-through” type applications.
To  install  cased  coils  in  upflow  applications,  follow  the  instructions
below (Upflow Coil Installation on p3).
To install cased coils in downflow applications, follow the instructions
below, (Downflow Coil Installation on p5).
See  Table 1  for  coil  connection  options.  Refer  to  instructions  for
placement of coil casing on furnace.
NOTE: We recommend a 4" transition for peak performance, but it is
not required unless stated.
WARNING
!
PERSONAL INJURY HAZARD
Failure to follow this caution may result in personal injury.
This  coil  contains  Nitrogen  precharge  of  7  –  10  PSIG.  Release  this
pressure through the center of the rubber plugs before removing plugs.
WARNING
!
EXPLOSION HAZARD
Failure  to  follow  this  warning  could  result  in
death,  serious  personal  injury,  and/or  property
damage.
Never use air or gases containing oxygen for leak
testing  or  operating  refrigerant  compressors.
Pressurized  mixtures  of  air  or  gases  containing
oxygen can cause an explosion.
CAUTION
!
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet  metal parts may  have sharp edges  or burrs.  Use care and wear
appropriate protective clothing and gloves when handling parts.
CAUTION
!
UNIT OR PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
Make sure that Aluminum tubes do not come in direct contact or allow
for  condensate  run  off with a dissimilar  metal. Dissimilar metals can
cause galvanic corrosion and possible premature failure.
CAUTION
!
ENVIRONMENTAL HAZARD
Failure to follow this caution may result in environmental damage.
Federal  regulations  require  that  you  do  not  vent  refrigerant  to  the
atmosphere. Recover during system repair or final unit disposal. 
Metal Clamp ONLY
Vapor Line
Sensing Bulb 
Indentation
TXV
Insulation Wire Tie
TXV Insulation 
Wrap