EVD4X, ESD4X, WMVC, WMSC: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
3
Installation of Evaporator Coils
Upflow Coil Installation
The cased coil is designed to fit furnaces of the same width (Fig. 2).
1. Set coil in place on upflow furnace discharge air opening.
2. Ensure coil is level for proper condensate drainage. Do not tip coil
toward condensate drain. Coil casing does not need to be fastened
or screwed to furnace.
3. When installing wider coil on narrower furnace, it is recommended
to use a transition adapter (Fig. 3).
NOTE:  On  upflow  installations  where  the  indoor  coil  is  placed  in  an
unconditioned space, a 6" wide piece of insulation should be applied and
wrapped around  the  outside of the coil casing  and supply  duct contact
point.  Consult  the  furnace  installation  instructions  for  any  special
requirements when installing the coil to the furnace.
CAUTION
!
IMPORTANT – UNCASED INSTALLATIONS
EVD4X and WMVC units are not intended to be installed uncased
in  a  plenum  and  must  be  installed  on  an  agency  listed  Furnace.
Failure to comply may damage the coil assembly and can result in
poor performance and property damage.
Any uncased V-Coil installation is not recommended due to factors
such as:
- Mounting dimensions must be held to ensure proper alignment 
between the coil and the condensate drain pan.
- Level installation and the relationship of the condensate drain 
pan and the coil. If the installation is not level and properly 
aligned, condensate blow-off could result.
- Unrestricted airflow across the coil is vital to adequate system 
performance.
- The factory-installed foil-faced insulation in the front and rear 
of the coil are required to prevent bypass airflow.
- Heat shields for the condensate drain pan (in upflow 
installations) and cross members (in downflow installations) 
must not be removed.
CAUTION
!
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
Installing coils rotated 90° from the front of the furnace, in upflow or
downflow applications, may cause water blow-off or coil freeze-up due
to the concentration of air on one slab of the coil or lack of air to a slab
of the coil. It is required that on this type of application, a field-supplied
adapter be placed between the coil and furnace to allow air to distribute
properly between all slabs of the coil.
Table 1 – Coil Connections / Orientations
Model
Nom. 
Tons
Line Set 
Connection Tube 
Size, in.
Flush Fit to 
Furnace Width, 
in. (mm)
Fits Next Smaller Furnace 
Width
90° 
Rotation to 
Furnace
(4" Min. 
Transition 
Required)
180° 
Rotation 
to Furnace
Suction Liquid
Equal 
Overhang
Offset 
Left
Offset 
Right
EVM4X24M17A1E / WMVM24417XA1E 2 3/4 3/8 17-1/2 (445) X X X
ALL
Upflow,
Downflow,
Horizontal Right,
Horizontal Left
EVM4X25M17A1E / WMVM25417XA1E 2 3/4 3/8 17-1/2 (445) X X X
EVM4X30M17A1E / WMVM30417XA1E 2.5 3/4 3/8 17-1/2 (445) X X X
EVM4X31M17A1E / WMVM31417XA1E 2.5 3/4 3/8 17-1/2 (445) X X X
EVM4X32M17A1E / WMVC32417XA1E 2.5 3/4 3/8 17-1/2 (445) X X X
EVM4X36M17A1E / WMVM36417XA1E 3 3/4 3/8 17-1/2 (445) X X X
EVM4X42M21A1E / WMVM42421XA1E 3.5 7/8 3/8 21 (533) X X X
EVM4X43M21A1E / WMVM43421XA1E 3.5 7/8 3/8 21 (533) X X X
EVM4X44M21A1E / WMVM44421XA1E 3.5 7/8 3/8 21 (533) X X X
EVM4X48M21A1E / WMVM48421XA1E 4 7/8 3/8 21 (533) X X X
EVM4X49M21A1E / WMVM49421XA1E 4 7/8 3/8 21 (533) X X X
EVM4X60M21A1E / WMVM60421XA1E 5 7/8 3/8 21 (533) X X X
EVM4X60M24A1E / WMVM60424XA1E 5 7/8 3/8 24-1/2 (622) X X X
EVM4X61M24A1E / WMVM61424XA1E 5 7/8 3/8 24-1/2 (622) X X X