EVD4X, ESD4X, WMVC, WMSC: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
5
A221110
Fig. 6 – 90° Rotation (shown in downflow)
4" Transition Required (not recommended)
A221111
Fig. 7 – 180° Rotation (shown in upflow)
(not recommended)
Downflow Coil Installation
NOTE: In downflow installation with a 4-way multipoise furnace, break
off  perforated  duct  flanges  on  furnace.  See  furnace  Installation
Instructions.
Refrigerant Line Connections
NOTE:  Factory  nitrogen  charge  may  escape  past  rubber  plugs  during
storage. This does not indicate a  leaking coil nor warrant return of the
coil.
Size and install refrigerant lines according to information provided with
outdoor  unit.  Coil  connection  tube  sizes  are  shown  in  Table 1.  Route
refrigerant  lines  to  the  coil  in  a  manner  that  will  not  obstruct  service
access to the unit or removal of the filter.
Do not use damaged, dirty, or contaminated tubing because it may plug
refrigerant  flow-control  device.  ALWAYS  evacuate  the  coil  and
field-supplied tubing before opening outdoor unit service valves.
Connect Refrigerant, Liquid, and Suction Lines
For  matched  and  mismatched systems, use line sizes  recommended  in
outdoor unit Installation Instructions.
The coil can be connected to outdoor units using field-supplied tubing of
refrigerant grade. Always evacuate tubing and reclaim refrigerant when
making  connections  or  flaring  tubing.  Leak  check  connections  before
insulating entire suction line.
See Table 1 for coil connection tube size.
1. Remove cabinet access door.
2. Remove rubber plugs, suction plug then liquid plug, from coil stubs
using a pulling and twisting motion. Hold coil stubs steady to avoid
bending or distorting.
Front of Coil
Front of 
Furnace
CAUTION
!
WATER MANAGEMENT HAZARD
Failure  to  follow  this  caution  could  cause  product  and/or  property
damage.
The  furnace  coil  door  must  be  properly  installed  when  the  coil  is  in
operation. To  ensure  proper  condensate  water  management,  the  drain
pan must  not touch the coil. When properly installed the furnace coil
door will correctly align the condensate pan with the coil.
WARNING
!
PERSONAL INJURY HAZARD
Failure to follow this warning could result in personal injury.
Wear  eye  protection.  Coil  is  factory  charged  with  7–10  psi  nitrogen.
The coil is under pressure and TXV screen is in place behind liquid line
plug. DO NOT remove liquid line plug first, always remove the suction
line plug first to depressurize the coil.
CAUTION
!
UNIT OR PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
Take  precautions  to  ensure Aluminum  tubes  do  not  come  in  direct
contact  or  allow  for  condensate  run  off  with  a  dissimilar  metal.
Dissimilar metals can cause galvanic corrosion and possible premature
failure.