58
Table 23 — Motormaster
®
V Program Parameters for Operating Modes
LEGEND
PARAMETER DESCRIPTION MODE 5 MODE 6 MODE 7 MODE 8
P01 Line Voltage: 01 = low line, 02 = high line 01 02 01 02
P02 Carrier Freq: 01 = 4 kHz, 02 = 6 kHz, 03=8 kHz 01 01 01 01
P03 Start-up mode: flying restart 06 06 06 06
P04 Stop mode: coast to stop 01 01 01 01
P05 Standard Speed source: 04=4-20 mA, 05=R22, 06=R134a 04 04 04 04
P06 TB-14 output: 01 = none 01 01 01 01
P08 TB-30 output: 01 = none 01 01 01 01
P09 TB-31 Output: 01 = none 01 01 01 01
P10 TB-13A function sel: 01 = none 01 01 01 01
P11 TB-13B function sel: 01 = none 01 01 01 01
P12 TB-13C function sel: 01 = none 01 01 01 01
P13 TB-15 output: 01 = none 01 01 01 01
P14 Control: 01 = Terminal strip 01 01 01 01
P15 Serial link: 02 = enabled 9600,8,N,2 with timer 02 02 02 02
P16 Units editing: 02 = whole units 02 02 02 02
P17 Rotation: 01 = forward only, 03 = reverse only 01 01 01 01
P19 Acceleration time: 10 sec 10 10 10 10
P20 Deceleration time: 10 sec 10 10 10 10
P21 DC brake time: 0 0000
P22 DC BRAKE VOLTAGE 0% 0000
P23 Min freq = 8 Hz ~ 100 - 160 rpm 8888
P24 Max freq 60 60 50 50
P25 Current limit: 125 125 110 110
P26 Motor overload: 100 100 100 100 100
P27 Base freq: 60 or 50 Hz 60 60 50 50
P28 Fixed boost: 0.5% at low frequencies 0.5 0.5 0.5 0.5
P29 Accel boost: 0% 0000
P30 Slip compensation: 0% 0000
P31 Preset spd #1: 0 57 57 47 47
P32 Preset spd #2: 0 0000
P33 Preset spd #3: 0 0000
P34 Preset spd 4 default – R22 setpoint. TB12-2 open 18.0 18.0 18.0 18.0
P35 Preset spd 5 default – R134a setpoint. TB12-2 closed 12.6 12.6 12.6 12.6
P36 Preset spd 6 default 0000
P37 Preset spd 7 default 0000
P38 Skip bandwidth 0000
P39 Speed scaling 0000
P40 Frequency scaling 50 or 60 Hz 60 60 50 50
P41 Load scaling: default (not used so NA) 200 200 200 200
P42 Accel/decel #2: default (not used so NA) 60 60 60 60
P43 Serial address 1111
P44 Password:111 111 111 111 111
P45 Speed at min signal: 8 Hz used when PID disabled and 4-20 mA input 8888
P46 Speed at max feedback: 60 or 50 Hz. Used when PID disabled and 4-20 mA input 60 60 50 50
P47 Clear history? 01 = maintain. (set to 00 to clear) 01 01 01 01
P48 Program selection: Mode 1 – 12 05 06 07 08
P61 PI Mode: 05= reverse, 0-5V, 01 = no PID 01 01 01 01
P62 Min feedback = 0 (0V *10) 0000
P63 Max feedback = 50 (5V * 10) 50 50 50 50
P64 Proportional gain = 4% 4444
P65 Integral gain = .2 .2 .2 .2 .2
P66 PI accel/decel (setpoint change filter) = 5 5555
P67 Min alarm 0000
P68 Max alarm 0000
NA Not Applicable
PID Proportional Integral Derivative
TB Terminal Block