OMD Technical Note TN20005
Carrier Fire & Security
8 Newmarket Court, Page 10 of 11
Chippenham Drive,
Kingston, Milton Keynes, MK10 0AQ
Business Confidential
6. All other enclosures (external view) and wiring used to connect the OMD relay contacts
to the vessel Alarm Monitoring & Engine Shutdown systems.
7. Document the software versions of all system components.
As part of this work document any concerns with:-
a. Corrosion.
b. Evidence of burnt components.
c. Poor quality wiring or incorrectly specified cabling used for power and data
communication.
d. Missing or incorrect EMC glands.
e. Missing or incorrect screening & earthing.
f. Missing blanking plugs or caps.
8. Inspect the contents of the Mk6 Event log.
It is important to understand the contents of the Mk6 Event log as diagnosing and removing
the reason for these fault Messages will be part of the Service visit.
On the Control Panel select Main Menu > 1. User > 3. Event Log > 1. List All Events
Using the up and down arrow keys scroll through the recent events.
9. Check the Status of each Detector prior to any cleaning taking place.
On the Control Panel select Main Menu > 1. User > 1. System Status > 2. Detector > 2.
Detector Status. Select the required Engine and Detector to access the Detector Status
Screen.