5
ERVXXLHB1200, HRVXXLHB1150, HRVXXLHB1250
17”
(432 mm)
17¼” (438 mm)
6”
(152 mm)
30¼” (768 mm)
35” (891 mm)
17”
(432 mm)
17¼” (438 mm)
6”
(152 mm)
34” (864 mm)
39” (991 mm)
ERV
HRV
1
2
3
4
1
2
3
4
1. Fresh air to house.
2. Exhaust air from house.
3. Fresh air from outside.
4. Exhaust air to outside.
A12341
PHYSICAL & ELECTRICAL DATA
MODEL
CAPACITY (LO---HI)
PORT
LOC.
CORE
WEIGHT
LBS. [KG]
VOLTAGE
MAX
POWER
WATTS
MAX
AMPS
CFM L/S TYPE AIR FLOW
ERVXXLHB1200 80 --- 198 38 --- 93 Ends
Enthalpic
transfer media
Cross flow 76 [35] 115/60/1 200 2.1
HRVXXLHB1150 66 --- 163 31 --- 77 Ends Polypropylene Cross flow 65 [30] 115/60/1 160 1.5
HRVXXLHB1250 82 --- 204 39 --- 96 Ends Polypropylene Cross flow 65 [30] 115/60/1 195 2.1
DEFROST OPERATION
MODEL
OUTSIDE TEMPERATURE DEFROST CYCLE (MIN.)
EXTENDED DEFROST CYCLES
(MIN.)
_C _F Defrosting
Operation Time
Between Ea ch
Defrost Cycle
Defrosting
Operation Time
Between Ea ch
Defrost Cycle
ERVXXLHB1200
--- 5 23 10 60 10 30
--- 1 5 5 10 30 10 20
--- 2 7 --- 1 7 10 20 10 15
HRVXXLHB1150
--- 5 23 7 50 10 30
--- 1 5 5 7 25 10 20
--- 2 7 --- 1 7 10 20 10 15
HRVXXLHB1250
--- 5 23 6 50 10 30
--- 1 5 5 6 25 10 20
--- 2 7 --- 1 7 10 20 10 15