FINAL CHECKS
IMPORTANT: Before leaving job, be sure to do the following:
1. Ensure that all wiring is routed away from tubing and sheet metal
edges to prevent rub-through or wire pinching.
2. Ensure that all wiring and tubing is secure in unit before adding
panels and covers. Securely fasten all panels and covers.
3. Tighten service valve stem caps to 1/12-turn past finger tight.
4. Leave Users Manual with owner. Explain system operation and
periodic maintenance requirements outlined in manual.
5. Fill out Dealer Installation Checklist and place in customer file.
CARE AND MAINTENANCE
For continuing high performance and to minimize possible equipment
failure, periodic maintenance must be performed on this equipment.
Frequency of maintenance may vary depending upon geographic areas,
such as coastal applications. See Owner's Manual for information.
Table 8 – Malfunction Lockout Durations
Code Title Time
24-58 5V PCM External Power Out of Range Duration of Event
25-61 Invalid Model Plug Malfunction Duration of Event
25-62 Model Plug Missing Malfunction Duration of Event
25-63 VFD Model Mismatch Permanent*
28-71 Fuse 1 Open Malfunction Permanent*
28-72 Fuse 2 Open Malfunction Permanent*
31-58
Compressor High Pressure Limit
Malfunction
4 hours
32-55 Compressor Low Pressure Limit Lockout 4 hours
32-59 Low Pressure Disable Permanent*
33-55 Compressor Low Discharge Limit Lockout 4 hours
34-58
Compressor High Temperature Limit
Malfunction
4 hours
35-58
Compressor High Compression Limit
Malfunction
4 hours
36-55
Compressor Low Compression Limit
Lockout
4 hours
38-53 Compressor Starting Malfunction 4 hours
38-54 Compressor No Pump 30 minutes
38-71 VFD Estimator Malfunction 4 hours
39-53 Fan Start Malfunction 4 hours
39-55 Unexpected Fan Shutdown Malfunction 4 hours
39-58 Fan Motor Malfunction 4 hours
53-41 OST Open / Low Temp Duration of Event
53-42 OST Shorted / High Temp Duration of Event
57-41 P1 Open Malfunction Duration of Event
57-42 P1 Shorted Malfunction Duration of Event
57-43 P1 Sensor Malfunction Permanent*
58-41 P2 Open Malfunction Duration of Event
58-42 P2 Shorted Malfunction Duration of Event
58-43 P2 Sensor Malfunction Permanent*
61-41 Reversing Valve Solenoid Open Duration of Event
64-41 EXV-H Phase Open Duration of Event
64-44 EXV-H Power Short to Ground Duration of Event
64-45 EXV-H Phase Short to Ground Duration of Event
65-41 EXV-VI Phase Open Duration of Event
65-44 EXV-VI Power Short to Ground Duration of Event
65-45 EXV-VI Phase Short to Ground Duration of Event
66-41 VFD Control Relay Coil Open Duration of Event
66-42 VFD Control Relay Coil Shorted Duration of Event
81-53 PFC Malfunction 4 hours
81-54 Unbalanced PFCM Malfunction 4 hours
81-58 VFD System Wiring Error 4 hours
82-53 VFD Reset with Power Dropout Malfunction 4 hours
82-55
VFD Shutdown with Power Dropout
Malfunction
4 hours
82-56 Low Voltage Shutdown Malfunction 4 hours
82-57 Line Over Voltage Malfunction 4 hours
83-55 Compressor Current Limit 3 Lockout 4 hours
83-56 Compressor Current Limit 4 Lockout 4 hours
83-57 Compressor Underspeed Shutdown 1 hours
84-58 VFD Overtemp Malfunction 4 hours
85-53 DC Under Voltage Malfunction 4 hours
85-54 DC Over Voltage Malfunction 4 hours
86-46 VFD Communication Malfunction 1 hour
87-53 VFD Initialization Malfunction 4 hours
88-55 Unexpected VFD Reset Malfunction 4 hours
88-71 VFD Internal Malfunction - Current Sensor 4 hours
88-73 VFD Internal Malfunction - DC Link Sensor 4 hours
88-74 VFD Internal Malfunction - PFCM Sensor A 4 hours
88-75 VFD Internal Malfunction - PFCM Sensor B 4 hours
88-76 VFD Internal Malfunction - Line Volt Sensor 4 hours
88-78 VFD Internal Malfunction - DC Discharge 4 hours
Table 8 – Malfunction Lockout Durations (Continued)
Code Title Time